19. TESTING THE LOCAL SYSTEM USING THE EKP1 or EKP1L:
Arm the system in the TEST MODE. (Press: Access Code, MODE,
TEST, then ENTER). The audible warning devices will pulsate con-
tinuously during TEST, except when testing an Entrance Delay zone.
During Entrance Delay time, the audible warning device will change
to a steady sound (for four seconds in the TEST MODE) and then
return to a pulsating sound. All loops may now be tested indepen-
dently. Violate each loop separately. The Arm and Zone LEDs will
flash on alarm. There is no need to reset panel after each zone test.
Bell or Siren will shut off in four seconds and another zone can be
tested.
NOTE: Zones violated as well as all other messages will not
report to the Central Reporting Station, while in the TEST
MODE. After all zones are tested, Disarm the panel. All au-
dible warning devices will shut off and the master Arm LED
will turn off.
20. TESTING COMMUNICATION TO THE CENTRAL REPORT-
ING STATION: Arm the Panel. Violate a zone. The Siren/Bell
should turn on, the zone and Arm LEDs should flash and the pre-
mises telephone should be inoperative (DEAD). After the Central
Reporting Station receives a good transmission of this violation, it
will send a Kiss-off signal back to the panel and the panel then
disconnects from the telephone line. Once the panel hangs up then
the local phones will be reconnected.
21. For additional information on EKP1 or EKP1L operation and re-
programming the access code, refer to the EKP1 or EKP1L Owner’s
Manual.
22. Fill in the appropriate information in the Owner’s Manual, and
give it to your customer when you explain how the system operates.
FIGURE 1 WIRING DIAGRAM
1.3 TROUBLESHOOTING
SYMPTOM CHECK
No indicators light Make sure system is connected to either a good battery or AC.
(Test battery under load). Check fuse F3.
Bells won’t ring Check Bell Fuse and Battery Fuse.
(Pre-alert pulsing) See “Fault Analysis” in EKP1/EKP1L User’s Manual. The "Fault Analysis" mode provides diagnostic
troubleshooting for AC power failure, low battery and failure to communicate. When the Green LED is flashing
and a "Zone Ready" LED is flashing that zone is in the "Trouble" or open condition.