Specifications
44
Sentinel 6 Rack
Technical data
Input
S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000
POWER POWER POWER
Input
S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000
POWER POWER POWER
Input voltage range 180-264 V
Input frequency tolerance ± 5%
Nominal voltage 220-230-240 V
Min. Voltage without battery discharging 170 V
Nominal frequency 50 / 60 Hz
Power factor >97%
Nominal current (A) 3,8 5 6,2 7,2 10 13,8 14,4 16
Output
S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000
POWER POWER POWER
Nominal power (VA/W) 700/490 1000/700 1000/700 1500/1050 2200/1540 2200/1540 3000/2100 3000/2100
Nominal voltage 220-230-240 V
Wave form sinusoidal
Voltage stability static 1,5%, dynamic ≤ 5%
Voltage distortion ≤ 3% (linear load), ≤ 6% (non-linear load)
Frequency 50/60 Hz +/- 2%
Crest factor 3:1
Overload 110% for 30 min, 130% for 30 s, 150% In for 10 s, > 150% for 500 ms
System
S6R 700 S6R 1000 S6R 1000 S6R 1500 S6R 2200 S6R 2200 S6R 3000 S6R 3000
POWER POWER POWER
Transfer time 0ms
AC-AC efficiency 86% 88%
Batteries: No./V/Ah 2/12/7 3/12/7 / 4/12/7 8/12/7 / 8/12/7 /
Communication ports RS232 + Communication slot (TCP/IP, HTTP, SNMP, JBUS, MODBUS, Profibus)
Protections overcurrent – short circuit – excessive battery discharge – overvoltage – undervoltage – overtemperature
Noise at 1 m <45 dBA
Operating temperature 0-40° C, optimal for batteries +15 ÷ +25°C
Standards safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23,
93/68, 89/336 EEC, EN 62040-3