Specifications

Input
S6-700 S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000
POWER POWER POWER
Technical dataSentinel 6
Power (VA/W) 700/490 1000/700 1000/700 1500/1050 2000/1400 2000/1400 3000/2100 3000/2100
Nominal voltage 220 - 230 - 240 V
Wave form sinusoidal
Voltage stabilty - steady state 1.5 %
Voltage stabilty - dynamic state < 5 % in 20 ms
Voltage distortion @ linear load 3%
Voltage distortion @ non-linear load (EN 50091-1-1) 5%
Frequency autosense
Frequency tolerance ± 0,2%
Crest factor 3 : 1
Overload 110% for 30 min, 130% for 30 s, 150% In for 10 s, > 150% for 500 ms
Output sockets No. 4 IEC 320 (10A) No. 6 IEC 320 (10A) No. 6 IEC 320 (10A)
No. 1 IEC 320 (16A)
Transfer time 0 ms
AC-AC efficiency 86% 88%
Batteries (No./V/Ah) 2/12/7 3/12/7 - 4/12/7 8/12/7 - 8/12/7 -
Communication ports RS232 + Communication Slot (TCP/IP, HTTP,SNMP, JBUS, MODBUS, PROFIBUS)
Protections excessive battery discharge - overcurrent - shortcircuit - overvoltage - undervoltage - overtemperature
Noise at 1mt < 45 dBA
Operating temperature 0 ÷ 40°C, optimal for batteries 15 ÷ 25°C
Standards
safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23, 93/68, 89/336 EEC, EN 62040-3
Battery charger (A) 1 1 4 1 1 8 1 8
Telephone line protection RJ45/RJ11 type filtered socket
Output
S6-700 S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000
POWER POWER POWER
System
S6-700 S6-1000 S6-1000 S6-1500 S6-2000 S6-2000 S6-3000 S6-3000
POWER POWER POWER
40
Input Rectifier
Nominal voltage 220 - 230 - 240 V
Min. Voltage without battery discharging 170 V
Nominal frequency 50 / 60 Hz
Power factor > 0,97
Nominal current (A) 2,7 3,6 4,8 7,2 7,5 10 10,5 14
Input bypass
Input voltage range 180-264 V
Input frequency tolerance ± 5%