Specifications

Power (VA) Model Back-up (min) Batteries Dimensions WxDxH (mm) Weight (kg)
500 e-Sentinel Rack 50 8 Internal 19”x450x2U 19
750 e-Sentinel Rack 75 5 Internal 19”x450x2U 19
1000 e-Sentinel Rack 100 5 Internal 19”x450x2U 19
1500 e-Sentinel Rack 150 6 Internal 19”x450x2U 26
2000 e-Sentinel Rack 200 6 Internal 19”x450x3U 34
Power (VA) Model Back-up (min) Batteries Dimensions WxDxH (mm) Weight (kg)
2000 Batt. exp. A7 18 5x7Ah 19”x440x3U 16
2000 Batt. exp. A12* 22 5x12Ah 19”x440x4U 23
37
e-Sentinel Rack
Input e-Rack 50 e-Rack 75 e-Rack 100 e-Rack 150 e-Rack 200
Technical data
Nominal voltage 220-230-240 V
Accepted voltage range -25% +21% (without battery discharging)
Input frequency 50/60 Hz (autosense)
Accepted frequency ±10%
Output e-Rack 50 e-Rack 75 e-Rack 100 e-Rack 150 e-Rack 200
System e-Rack 50 e-Rack 75 e-Rack 100 e-Rack 150 e-Rack 200
Battery cabinets for longer autonomy
Note
1U= 44,43 mm
19”= 483 mm
* With built-in battery charger to reduce recharging time.
Power (VA/W) 500/335 750/500 1000/670 1500/1000 2000/1340
Nominal voltage (in battery operation) 230 V ±5%
Nominal voltage (in mains operation) the AVR circuit regulates the output voltage from +11%
to –15% with input variation of -25% +21 %
Wave form sinewave
Distortion <2%
Frequency in battery operation 50/60 Hz autosetting, ±1%
Output sockets No. 4 IEC 320 (10A)
Transfer time 2 ms
Batteries (No./V/Ah) 2/12/7 2/12/7 2/12/9 4/12/7 5/12/7
Battery type maintenance free sealed lead-acid
Battery recharging time 8 h
AC-AC efficiency 98%
Communication port
USB, RS232, Slot for Netman 102, Multicom 302, Multicom 352, Profibus
Protections overcurrent – short circuit – excessive battery discharge – overvoltage
undervoltage - overtemperature
Noise at 1 m <40 dBA
Operating temperature 0÷40° C, optimal for batteries +15÷+25 °C
Humidity 90% non-condensing
Standards safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23, 93/68,
89/336 EEC, EN 62040-3, surge IEC 801-5
Telephone line protection RJ45/RJ11 type filtered socket