Specifications
e-Sentinel
35
Input e 50 e 75 e 100 e 150 e 200
Technical data
Nominal voltage 230 V
Accepted voltage range -25% +21% (without battery discharging)
Input frequency 50/60 Hz (autosense)
Accepted frequency ±10%
Output e 50 e 75 e 100 e 150 e 200
System e 50 e 75 e 100 e 150 e 200
Transfer time 2 ms
Batteries (No./V/Ah) 2/12/7 2/12/7 2/12/9 4/12/7 5/12/7
Battery type maintenance free sealed lead-acid
Battery recharging time approx 8 h
AC-AC efficiency 98%
Communication port USB, RS232, Slot for communication cards
Protections overcurrent – short circuit – excessive battery discharge – overvoltage
undervoltage - overtemperature
Noise at 1 m <40 dBA
Operating temperature 0÷40 °C , optimal for batteries +15 ÷ +25 °C
Humidity 90 % non-condensing
Standards safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23,
93/68, 89/336 EEC, EN 62040-3, surge IEC 801-5
Telephone line protection RJ45/RJ11 type filtered socket
Power Model Back-up Batteries Dimensions Weight
(VA) (min) WxDxH (mm) (kg)
500 e-Sentinel 50 8 Internal 158x400x231 13
750 e-Sentinel 75 5 Internal 158x400x231 14
1000 e-Sentinel 100 5 Internal 158x400x231 14
1500 e-Sentinel 150 6 Internal 158x400x231 20
2000 e-Sentinel 200 6 Internal 158x485x340 25
Power Model Back-up Batteries Dimensions Weight
(VA) (min) WxDxH (mm) (kg)
Battery cabinets for longer autonomy
Power (VA/W) 500/335 750/500 1000/670 1500/1000 2000/1340
Nominal voltage (in battery operation) 230 V ±5%
Nominal voltage (in mains operation) the AVR circuit regulates the output voltage from +11%
to –15% with input variation of -25% +21%
Wave form sinewave
Voltage distortion <2%
Frequency variation (in battery operation) 50/60 Hz autosetting , ±1%
Output sockets No. 4 IEC 320 (10A)
2000 Batt. exp. S5 A7 20 5x7Ah 158x565x340 16
2000 Batt. exp. S5 A12 30 5x12Ah 158x565x340 24