33
Input Syncro 800 Syncro 1000 Syncro 1500 Syncro 2000
Technical data
Nominal voltage 230 V
Accepted voltage range +20% -25%
Input frequency 50/60 Hz (autosense)
Accepted frequency ±5%
Output Syncro 800 Syncro 1000 Syncro 1500 Syncro 2000
Power (VA/W) 800/480 1000/600 1500/900 2000/1200
Nominal voltage (in battery operation) 230 V ±5%
Nominal voltage (in mains operation) the AVR circuit regulates the output voltage from +17% to –15%
with input variation of ±25%
Wave form step-wave
Output sockets No. 4 IEC 320 (10A)
System Syncro 800 Syncro 1000 Syncro 1500 Syncro 2000
Transfer time 2 ms typical, 4 ms max.
Batteries (No./V/Ah) 2/12/7 2/12/7 2/12/9 3/12/9
Battery type maintenance free sealed lead acid
Battery recharging time 6-8 h
AC-AC efficiency 99%
Communication port RS232
Protections overcurrent – short circuit – excessive battery discharge
Noise at 1 m <40 dBA
Operating temperature 0÷40°C, optimal for batteries +15÷+25°C
Relative humidity 0÷90 % non condensing
Standards safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23,
93/68, 89/336 EEC, EN 62040-3
Telephone line protection RJ45/RJ11 type filtered socket
Power Model Back-up Batteries Dimensions Weight
(VA) (min) WxDxH (mm) (kg)
800 Syncro 800 5 Internal 140x375x180 14
1000 Syncro 1000 6 Internal 140x375x180 14
1500 Syncro 1500 6 Internal 140x375x180 15
2000 Syncro 2000 6 Internal 140x410x214 20