Specifications
PC Planet
31
Input PC Planet 400 PC Planet 400S PC Planet 550S PC Planet 650S
Technical data
Nominal voltage 230 V
Voltage range +25% -25% (without battery discharging)
Input frequency 50/60 Hz (autosense)
Accepted frequency ±5%
Output PC Planet 400 PC Planet 400S PC Planet 550S PC Planet 650S
System PC Planet 400 Planet 400S PC Planet 550S PC Planet 650S
Transfer time 2 ms typical, 4 ms max.
Batteries (No./V/Ah) 1/12/4 1/12/4 1/12/7 1/12/9
Battery type maintenance free sealed lead-acid
Battery recharging time 6-8 h
AC-AC efficiency 99%
Communication port – RS232
Protections overcurrent – short-circuit – excessive battery discharge
Noise at 1 m <40 dBA
Operating temperature 0÷40 °C optimal for batteries +15÷+25°C
Relative humidity 0÷90 % non condensing
Standards safety EN 62040-1, EMC IEC 62040-2 and EN 50091-2 lev. B, Directives 73/23,
93/68, 89/336 EEC, EN 62040-3
Marks CE ; GS/TÜV
Telephone line protection – RJ45/RJ11 type filtered socket
Power Model Back-up Batteries Dimensions Weight
(VA) (min) WxDxH (mm) (kg)
400 PC Planet 400 6 Internal 110x325x152 5,8
400 PC Planet 400S 6 Internal 110x325x152 5,9
550 PC Planet 550S 6 Internal 110x325x152 6,2
650 PC Planet 650S 6 Internal 110x325x152 6,3
Power (VA/W) 400/240 400/240 550/330 650/400
Nominal voltage (in battery operation) 230 V ±5%
Nominal voltage (in mains operation) the AVR circuit regulates the output voltage from +17% to –15%
with input variation of ±25%
Wave form step-wave
Output sockets No. 3 IEC 320 (10A)