Specifications
85
Technical dataSentry MPS FC
Three-phase input
Single-phase output
Models MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120
Power (kVA) 30 60 80 100 120
Input MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V ± 20%
Frequency 45 ÷ 65 Hz
Power factor ≥0.93 (in the Plus version)
Current harmonic distortion (THDi) <5% (in the Plus version)
Soft start 0 ÷ 100% in 120’’ configurable
Output MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120
Rated power (kVA) 30 60 80 100 120
Active power (kW) 24 48 64 80 96
Nominal voltage 208Vac 3Ph + N (settable 200 V)
Static stability ±1%
Dynamic stability ± 5%
Voltage distortion with linear load <3%
Voltage distortion with non linear load <4%
Frequency 400 Hz
Crest factor (Ipeak/Ipms) 3:1
Overload 110% for 60’; 125% for 10’; 150% for 1’
System MFC400-30 MFC400-60 MFC400-80 MFC400-100 MFC400-120
Remote signalling Voltage-free contacts
Remote commands EPO and ON/OFF
Communication Double RS232 + remote contacts + 2 communication interface slots
Efficiency Up to 92%
Dimensions (wdh) (mm) 550x740x1200 800x800x1900
Weight (kg) 330 480 500 530 560
Noise level 61 to 63 dBA at 1 m
Operating temperature 0 °C to 40 °C (50°C @ 75% load)
Relative humidity <95% non condensing
Protection degree IP20
Colour Light grey (RAL 7035)
Compliance Safety: EN 62040-1-1 (Directive 2006/95/EC);
EMC: EN 62040-2 (Directive 2004/108/EC)
Classification as per IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111