Specifications

80
Technical dataSentry MPS-HP
Three-phase input
Three-phase output
Models MPS-HP 100 MPS-HP 120 MPS-HP 160 MPS-HP 200 MPS-HP 250
Power (kVA) 100 120 160 200 250
Input MPS-HP 100 MPS-HP 120 MPS-HP 160 MPS-HP 200 MPS-HP 250
Nominal voltage 380 - 400 - 415 Vac three-phase
Range acceptable without battery intervention 300 ÷ 480 Vac
Frequency 45 ÷ 65 Hz
Power factor >0.99
Current harmonic distortion <2.5% THDi
Soft start 0 ÷ 100% in 30’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from the front panel)
Standard features Back Feed protection; separable bypass line
Output MPS-HP 100 MPS-HP 120 MPS-HP 160 MPS-HP 200 MPS-HP 250
Rated power (kVA) 100 120 160 200 250
Active power with load PF from 0,9 cap. to 0,8 ind. (kW) 80 96 128 160 200
Number of phases 3 + N
Nominal voltage 380 - 400 - 415 Vac three-phase + N
Static stability ±1%
Dynamic stability ± 5% in 10 msec.
Voltage distortion with linear load 1%
Voltage distortion with non linear load 3%
Frequency stability on battery 0.05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
Battery MPS-HP 100 MPS-HP 120 MPS-HP 160 MPS-HP 200 MPS-HP 250
Type Free lead-acid, and VRLA AGM / GEL; NiCd
AC ripple current Zero
Temperature compensation -0,5 Vx °C
System MPS-HP 100 MPS-HP 120 MPS-HP 160 MPS-HP 200 MPS-HP 250
Remote signalling Voltage-free contacts (configurable)
Remote commands EPO and bypass (configurable)
Communication Double RS232 + remote contacts + 2 slots for communication interface
Efficiency Smart Mode Up to 98%
Dimensions (wdh) (mm) 800x850x1900 1000x850x1900
Weight (kg) 656 700 800 910 1000
Noise level 63 ÷ 68 dBA at 1 m
Operating temperature 0 °C ÷ +40 °C
Relative humidity <95% non condensing
Protection degree IP20 (others on request)
Colour Light grey (RAL 7035)
Compliance Safety: EN 62040-1-1 (directive 2006/95/EC);
EMC: EN 62040-2 (directive 2004/108/EC)
Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111