Specifications

76
Technical dataSentry MPS
Three-phase input
Three-phase output
Models MPS 100 MPS 120 MPS 160 MPS 200
Power (kVA) 100 120 160 200
Input MPS 100 MPS 120 MPS 160 MPS 200
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V ± 20%
Frequency 45 ÷ 65 Hz
Soft start 0 ÷ 100% in 30’’ configurable
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from the front panel)
Standard features Back Feed protection; separable bypass line
Output MPS 100 MPS 120 MPS 160 MPS 200
Rated power (kVA) 100 120 160 200
Active power with load PF from 0,9 cap. to 0,8 ind. (kW) 80 96 128 160
Number of phases 3 + N
Nominal voltage 380 - 400 - 415Vac three-phase + N
Static stability ±1%
Dynamic stability ± 5% in 10 msec.
Voltage distortion with linear load 1%
Voltage distortion with non linear load 3%
Frequency 50 or 60 Hz configurable
Waveform Sinusoidal
Crest factor (Ipeak/Ipms) 3:1
Overload 110% for 60’; 125% for 10’; 150% for 1’
Battery MPS 100 MPS 120 MPS 160 MPS 200
Type Lead, open vase acid and VRLA, AGM / GEL; NiCd
AC ripple current Zero
Temperature compensation -0,5 Vx °C
System MPS 100 MPS 120 MPS 160 MPS 200
Remote signalling Voltage-free contacts (configurable)
Remote commands EPO and bypass
Communication Double RS232 + remote contacts + 2 communication interface slots
Efficiency Smart Mode Up to 98%
Dimensions (wdh) (mm) 800x800x1900
Weight (kg) 640 650 770 810
Noise level 63 ÷ 68 dBA a 1 m
Operating temperature 0 °C / +40 °C
Relative humidity <95% non condensing
Protection degree IP20
Colour Light grey (RAL 7035)
Compliance European Directives: L V 2006/95/EC Low voltage directive
EMC 2004/108/EC Electromagnetic compatibility directive
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111