Specifications
70
Models HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Power (kVA) 8 10 15 20 30 40 60 80 100
Technical data
Sentry HPS
Three-phase input
Single-phase output
Input HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Rated voltage 400 Vac three-phase
Voltage range ± 20%
Frequency range 45 ÷ 65 Hz
Power factor > 0.92 with harmonic filter
Current harmonic distortion < 5% with harmonic filter
Soft start 0-100% in 10”
By pass HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Rated voltage 230 Vac single-phase
Permitted voltage range ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz
Permitted frequency range ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard features BackFeed protection; split bypass line
Batteries HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Type Maintenance-free lead-acid VRLA AGM / GEL; NiCd
Maximum recharge current (A) 0,2xC10
AC ripple voltage <1%
System HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Weight (kg) From 190 From 200 From 220 From 230 290 340 440 520 650
to 460 to 470 to 490 to 500
Dimensions (wdh) (mm) 555x720x1200 800x740x1400 1070x
740x1400
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + remote contacts
Operating temperature O °C / +40 °C
Relative humidity < 95% non condensing
Colour Light grey (RAL 7035)
Noise 54 dBA at 1 m 60 dBA at 1 m 65 dBA at 1 m
Protection degree IP20
Efficiency Smart Mode up to 98%
Compliance Safety: EN 62040-1-1 (Directive 2006/95/EC); EMC: 6200-2 (Directive 2004/108/EC)
Internal batteries Yes Yes Yes Yes No No No No No
Inverter output HM8 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100
Rated power (kVA) 8 10 15 20 30 40 60 80 100
Active power (kW) 6.4 8 12 16 24 32 48 64 80
Number of phases 1
Rated voltage (V) 230 Vac single-phase
Regulation of the output voltage 220 ÷ 244 Vac phase/neutral (from control panel)
Crest factor (Ipeak/Irms) 3 : 1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60 Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1’
Frequency stability ± 0,05% on mains failure
± 2% (selectable from ± 1% to ± 5%) with mains supply present