Specifications
58
Technical dataFlexus
Three-phase input
Three-phase output
Models FT 10 FT 12 FT 15 FT 20 FT-H 30 FT-H 40 FT100 FT120
Power (kVA) 10 12 15 20 30 40 100 120
Input FT 10 FT 12 FT 15 FT 20 FT-H 30 FT-H 40 FT100 FT120
Rated voltage 380- 400-415 Vac three-phase +N
Rated frequency 50/60 Hz
Frequency tolerance 40 ÷ 72 Hz
Power factor at full load 0.99
Current distortion THDI ≤ 3%
By pass FT 10 FT 12 FT 15 FT 20 FT-H 30 FT-H 40 FT100 FT120
Rated voltage 380-400-415 Vac three-phase +N
Number of phases 3 + N
Voltage tolerance 180 ÷ 264V (selectable)
Rated frequency 50 or 60 Hz (selectable)
Frequency tolerance ±5 (selectable)
Batteries FT 10 FT 12 FT 15 FT 20 FT-H 30 FT-H 40 FT100 FT120
Type VRLA AGM/GEL
Recharge time 6 h
Output FT 10 FT 12 FT 15 FT 20 FT-H 30 FT-H 40 FT100 FT120
Rated power (kVA) 10 12 15 20 30 40 100 120
Active power with load PF from 0,9 cap. to 0,9 ind.
9 10.8 13.5 18 27 36 90 108
Output power factor 0.9
Number of phases 3 + N
Rated voltage 380-400-415 Vac (selectable)
Static variation ± 1%
Dynamic variation ± 3%
Crest factor (Ipeak/Irms) 3 : 1
Voltage distortion ≤ 1% with linear load / ≤ 3% with non-linear load
Frequency 50/60 Hz
Frequency stability on battery mode 0.01%
Overload at Pf 0.8 115% unlimited, 125% for 10 minutes, 150% for 1 minute, 168% for 5 seconds