Specifications

Models FM 10 FM 12 FM 15 FM 20
Power (kVA) 10 12 15 20
Input FM 10 FM 12 FM 15 FM 20
Rated voltage 380- 400-415 Vac three-phase with Neutral / 220-230-240Vac single-phase
Rated frequency 50/60 Hz
Frequency tolerance 40 ÷ 72 Hz
Power factor at full load 0.99
Current distortion THDI 3%
By pass FM 10 FM 12 FM 15 FM 20
Rated voltage 220-230-240 Vac
Number of phases 1
Voltage tolerance 180 ÷ 264V (selectable)
Rated frequency 50 or 60 Hz (selectable)
Frequency tolerance ±5 (selectable)
Batteries FM 10 FM 12 FM 15 FM 20
Type VRLA AGM/GEL
Recharge time 6 h
Output FM 10 FM 12 FM 15 FM 20
Rated power (kVA) 10 12 15 20
Active power with load PF from 0,8 cap. to 0,8 ind.
8 9.6 12 16
Output power factor 0.8
Number of phases 1
Rated voltage 220-230-240 Vac (selectable)
Static variation ± 1%
Dynamic variation ± 3%
Crest factor (Ipeak/Irms) 3 : 1
Voltage distortion 1% with linear load / 3% with non-linear load
Frequency 50/60 Hz
Frequency stability on battery mode 0.01%
Overload at Pf 0.8 110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds
56
Technical dataFlexus
Three-phase or single-phase input
Single-phase output