Specifications
FLEXIBILITY
Flexus is suitable for use in a broad
spectrum of applications, thanks to a
variety of configurations, accessories
and options providing flexibility and a
choice of performance levels:
• suitable for powering capacitive loads,
such as blade servers, without any
reduction in active power
(0.9 in lead to 0.9 lag)
• multiple operating modes: On Line,
Eco, Smart Active and Stand By Off
• Frequency converter mode
• configurable Power Share connections
to ensure backup for the most critical
loads or programmed to operate only
when mains power fails
•
Cold Start facility that starts the UPS
even when it is not connected to the mains
• FT/FM H version: in cabinet 440x850
x 1320 WDH, it provides optimum
solutions when medium or long term
runtime is required
• optional temperature sensor for
external battery cabinets, to assist the
recharge voltage compensation
• additional battery chargers to optimise
recharge times
•
optional dual input to mains power supply
• isolation transformer options to vary
neutral connectivity in the event of
separate power sources or for
galvanic isolation between input
and output
•
battery cabinets of various sizes and
capacities to ensure prolonged runtime.
ADVANCED COMMUNICATION
Flexus is equipped with a graphic display
that provides information, measures,
states and alarms regarding the UPS in
5 different languages.
• Advanced multiplatform
communication, for all operating
systems and network environments:
Watch&Save 3000 monitoring and
shutdown software included with for
Windwows 2008, Vista, 2003, XP;
Mac OS X, Linux, Novell and most
popular Unix operating systems
• Compatible with PowerNetGuard for
the remote assistance service
RS232 or USB serial port
• 3 slots for the installation of optional
communication accessories such as
SUITABLE FOR
EMERGENCY LIGHTING
APPLICATIONS
54
Flexus Output Power
Reactive Power
-1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1
1,00
0,75
0,50
0,25
Leading Cosϕ (capacitive loads)
cosϕ 0,9 cosϕ 1
100% kW
cosϕ 0,9
100% kVA
Lagging Cosϕ (inductive loads)
Active Power
UPS @ Cosϕ 0,9
Es. 20kVA - 18kW !!!
network adapter and volt-free contacts.
• REPO (Remote Emergency Power Off)
• Input for synchronization from an
external source
• Graphic mimic panel display for remote
connection
• Input for connection of the auxiliary
contact of an external manual bypass