111
ELC Line Conditioners
ELC 1500 ELC 3000 ELC 5000
Technical data
Nominal input voltage 220/230/240 Vac single-phase
Nominal output voltage 220/230/240 Vac selectable, single-phase
Input voltage range -18% +14% depending on the selected output voltage
Input frequency 48 - 62 Hz
Power (kVA) 1,5 3 5
Max. output current at 230V (A) 7 14 22
Efficiency 95%
Accuracy ±3%
Regulation speed (ms/Volt) 2
Overload 1,5 I
N
x 5 sec
Accepted load variation 0 to 100%
Load power factor Any
Harmonic distortion <0,5%
Input peak voltage protection Up to 4KV - 130 Joule
Common mode rejection ratio 70 dB
Primary and secondary insulation voltage 2500V input/output
Cooling Natural Forced ventilation
Operating ambient temperature 0°C ÷ 40°C
Protection degree IP 20
Display indications Line OK, load level, overload, alarms
Acoustic alarm Active for overload, overvoltage, overtemperature
Input protection Automatic switch
Output protection Fuses
Input connection Internal terminal board
Output connection Internal terminal board
ELC 1500 ELC 3000 ELC 5000
Dimensions (wdh) (mm) 230x350x275 340x540x310
Weight (kg) 26 44 56