Specifications
107
Voltronic 4 single-phase
Technical data
V4-500 V4-1000 V4-2000 V4-4000 V4-5000 V4-10000
Nominal output voltage 220-230-240 Vac single-phase
Input voltage range -18% +14% depending on the selected output voltage
Frequency 48 -62 Hz
Power (kVA) 0,5 1 2 4 5 10
Maximum output current at 230V (A) 2,4 4,5 9 18 22 44
Efficiency 98%
Accuracy ±3%
Regulation speed (ms/V) 2
Accepted load variation 0 to 100%
Load power factor Any
Overload 1,5 I
N
x 5 sec
Harmonic distortion <0,5%
Cooling Natural Forced ventilation
Operating ambient temperature 0°C ÷ 40°C
Protection degree IP 20
Display indications Mains OK, load level, overload, alarms
Acoustic alarm Active for overload, over-voltage, over-temperature
Input protection Fuse Automatic switch
Output protection Fuse Fuse
Input connection Cable with Schuko plug Internal terminal board
Output connection Schuko socket Internal terminal board
V4-500 V4-1000 V4-2000 V4-4000 V4-5000 V4-10000
Dimensions (wdh) mm 180x215x194 230x350x275 340x540x310
Weight (kg) 9 10 21 25 27 51