Specifications
102
CSS Configurations
Standby Power Systems
AROS uninterruptible power supplies
are also designed and built for use in
applications such as central supply
systems for emergency lighting,
security alarms and electro-medical
equipment.
The CEI 64-8 V2, EN 50171 standards
and other guidelines set down the
characteristics and performance levels
required from such systems. The main
ones are summarized below:
• Up to 3 h back-up times
• Battery recharge time of under 12 h
• Galvanically isolated input/output
• High-level diagnostics – preferably
from a front mimic panel
• Remote interface – normally volt-free
contacts
• High short circuit current capability.
The applications require a continuous
power system configured as follows:
• A standard UPS with high capacity
battery charger
• An isolation transformer (option)
• A remote interface to communicate
with other peripherals.
1. Always powered
2. Powered from the mains
3. Emergency only
4. Always powered/Emergency only
Diagrams of the various system solutions