Start-Up Check Lists
Steam Dispersion type:
 □Humidipack  □Expresspack □Fanpackage(EHF)
 □DispersionTube □DispersionTubewithDrain
 □Other____________________________________________
Plumbing:
  Inlet Water:
  □Inletwaterpressurebetween25-120psig
Drain Lines:
  Size: ________
  □Airgaplocatedwithin3’ofhumidifier
  □Linepitched1”per12”awayfromhumidifier
  □Temp-R-Drain(condensatecooler)
  □Othercondensatecooler______________________________
Wiring:
 □Allwiresconnectedsecurely
 □NoloosewiresaroundPCboard
 □ProperbreakerandwiresizeperTable7-1and7-2ofHC6000IOM
Control Wiring:
 Installed
  □HighLimitHumidistat
  □Mounted10feetdownstreamofdispersion
  □Airproving/pressureswitch
  □Mountedupstreamofdispersion
  □ModulatingHumidistat/Controller
  Signal Type:
  □0-10VDC□4-20mA
  □Communications
  □Modbus □BACnet □LonWorks