Troubleshooting guide

52
Table 52-1. BACnet Variable List
BACnet data type address
description Value / (unit) attribute
1Fill valve status
0:off 1:on
2Drain valve status
0:off 1:on
3contactor 1 status
0:off 1:on
4contactor 2 status
0:off 1:on
5contactor 3 status
0:off 1:on
6contactor 4 status
0:off 1:on
8Network control
0:Local 1:Remote
1comm type
0:485 1:PSP
2Sensor select
0:Humidistat 1:RH sensor
3High limit sensor select
0:not use 1:use
4Outside temperature
0:not use 1:use
5Network enable
0:disable 1:enable
6Modulating Fill enable
0:enable 1:disable
1Desired RH / Demand
(%)
2Steam Output
(kg/hr)
3Water level
0:low 1:normal 2:high 3:exception
4 Run status
0:Idle 1:Steam gen. 2:Cycle drain 3:End of season drain 4:Bed dring 5:Failure 6:Drain 7:heat 8:Manual drain
9:Fill 10: Test 11: Manual stop 12: Empty drain
5
Bed life(hours)
6
Bed life(Minutes)
7
Run Time (hours)
8
Run Time (Minutes)
9
Drain Freq (hours)
10
Drain Freq (Minutes)
11
Idle Time (hours)
12
Idle Time (Minutes)
13
RH / Demand (Analog input)(%)
14
Duct value (%)
15
Outside temperature()
16
Water temperature()
17
Heat temperature()
18 Failure
1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit have reached
100% of bed life 5:Fill time out to low level 6:Water level dropped below level during normal run 7:Fill time
out from low to high level
19
Contactor number 1,2,3,4
20
Heating Element Power 0:1000W 1:3000 2:5000W 3:6650W 4:8000W
1Language Select
0:English 1:Chinese
2Set RH / Demand
(%)
3Duct High Limit set point
(%)
4Outside temp. high set point
()
5Outside temp. low set point
()
6Outside RH low set point
(%)
7Run mode
0:Steam Gen 1:Manual Drain 2:Manual Fill 3:Unit stop
8AQUASTAT
()
9Bed Life
0:500hours 1:750hours 2:1000hours 3:1250hours 4:1500hours 5:1750hours 6:2000hours 7:2250hours
8:2500hours 9:3000hours 10:No bed
10 Drain Cycle
0:6hours 1:12hours 2:24hours 3:48hours 4:96hours 5:Real time drain
11 Drain duration
0:1Minutes 1:5Minutes 2:10Minutes
12 Signal type
0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA
13 PID_DIV
14 PID_PB
15 PID_SI
(second)
16 PID_DG
17 Modulating Fill Cycle
(second)
18 Modulating Fill duration
(second)
19 Water temp. compensate
()
20 Themocouple compensate
()
analog ouput
BACNet variants list
binary input
binary output
Analog input
read only
read / write
read only
read / write