Troubleshooting guide
42
Resistance Value of 6100/6300 Components
Component Voltage Resistance
Fill Valve 24Vac 18W
Drain Valve 24Vac 10W
Contractor 24Vac 7-9W
Thermocouple in Heating Elements - 0.51W
Heating Elements
208Vac and 380Vac 3kW 220Vac 46.0-48.6W
240Vac and 380Vac 3kW 240Vac 55-58W
480Vac and 380Vac 3kW 277Vac 72-78.2W
600Vac and 380Vac 3kW 346 Vac 112.4-122.4W
208Vac and 380Vac15/30kW 220Vac 9.2-10.7W
240Vac 15/30kW 240Vac 10.9-12.6W
480Vac 15/30kW 277Vac 14.5-16.8W
600Vac 15/30kW 346Vac 22.7-26.3W
208Vac and 380Vac9/18kW 220Vac 15.3-17.7W
240Vac 9/18kW 240Vac 18.2-21.1W
480Vac 9/18kW 277Vac 24.3-28.2W
600Vac 9/18kW 346Vac 37.9-43.9W
Power Transformer
120Vac 13.6W across H1-H2
15.1W across H3-H4
208Vac 22W across H1-H2
240Vac 29W across H1-H2
380Vac 77W across H1-H2
480Vac 125W across H1-H2
600Vac 194W across H1-H2
Power Transformer
(secondary)
All 
Voltage
0.6W across X1-X2
0.4W across X1-X2
Resistance Value of 6500/6700 Components
Component Voltage Resistance
Fill Valve 24Vac 8.8W
Drain Valve 24Vac 4.1W
Thermocouple in Heating Elements - 0.51W
Heating Elements
208, 240, 380V, 30/33, 5/40/45/50, 3/60kW 240Vac 7.4-9.1W
380V 48/72/96kW 220Vac 5.2-6.3W
480V 48/72/96kW 277Vac 8.1-10.0W
600V 48/72/96kW 346 Vac 12.8-15.7W
Power Transformer
Primary Loop
208Vac 18W across H1-H2
240Vac 21W across H1-H3
277Vac 24W across H1-H4
380Vac 40W across H1-H5
480Vac 22W across H1-H6
600Vac 22W across H1-H2
Secondary Loop
208Vac 1W across X1-X2
240Vac 1W across X1-X2
277Vac 1W across X1-X2
380Vac 1W across X1-X2
480Vac 1W across X1-X2
600Vac 1W across X1-X2
Note: All measurements should be made with the main power off 
and the wires to the component being tested disconnected.
Resistance Values of Components