Troubleshooting guide
21
9.  Operate the unit configuration menu “EOL Reset”, to reset the ionic bed life. All the 
  accumulated ionic bed time has been reset to zero. The unit should now be heard filling.  
  NOTE: The accumulated ionic bed time can be reset to zero at anytime. However, the unit   
  should not be reset without first inspecting the ionic beds.
10. After the unit has heated up and started making steam, turn main power off and double check tank 
  access panel gasket for steam leakage. Hand tighten wing nuts or reposition gasket if necessary.
Cleaning the Water Level Electrodes
1.  If there is water in the steam generating tank, operate menu to “MANUAL DRAIN”. The drain valve 
  should energize, and the unit should completely drain.
2.  After the tank has drained, turn off the main   
  power at the disconnect.
3.  Unclamp and remove the 5/8” ID Silicone tubing 
  from the top outlet of the level canister.
4.  Disconnect wires #21 (high level probe), #20   
  (low level probe) and #19 (common probe) from 
  the probes, noting the probe and wire locations. 
  Note: Level control float switches are used   
  for DI, RO, or very pure water. Cleaning   
  should not typically be required.
5.  Unscrew the probes from the level canister   
  using the hex nut fitting on the probe 
  (Note: Level canister bushings may be removed with the probes, if necessary).
6.  Use a wire brush, wire wheel, or similar means to clean scale deposits off the stainless steel tip of  
  the probe. Cleaning of the Teflon insulating jacket (white portion) should not be needed.
7.  Wipe probes with a clean dry cloth.
8.  Inspect the interior of the level canister. If large amounts of scale or debris are present, remove the 
  canister from the cabinet by removing the two clamping bracket screws and disconnecting the 5/8”  
  ID Silicone hose at the bottom of the canister. Flush the canister with water to remove debris 
  and reinstall.
9.  Reinstall the probes and probe wires in their proper locations. The high water probe (shortest)   
  goes in the right hole of the canister. The low water probe (medium length) goes in the left front   
  hole of the canister. The common probe (longest) goes in the left, rear hole of the canister.
10. Reconnect the 5/8” ID Silicone hose(s).