Troubleshooting guide
18
Maintenance
When 90% of the setting service time has accumulated, the “STATE” LED on the control panel will 
blink in yellow. (Refer to EOL settings, for bed life duration settings). If the HumidiClean is not serviced 
at this time; the unit will continue to operate for the remaining 10% of the service life setting. When 
100% of the bed life setting has been reached, the “STATE” LED will be on in red. The unit will drain 
the tank and not respond to a call for demand.
Note: Service Life can be adjusted based on water quality. If Ionic Beds are relatively free of scale 
deposits or scale is forming on tank walls and elements because beds are saturated with scale, please 
consult the factory for Service Life adjustment procedures.
A. Servicing the Unit
  1. Save the settings, consult the OPERATION SETUP menu
  2. Go to Steam Gen. Menu
    a. Drain tank by changing from “STEAM GEN.” to “MANUAL DRAIN” in the Operation   
     Setup Menu.
    b. Once the tank is drained, shut power off to unit and allow the tank to cool.
    c. Remove the cabinet access panel and tank access panel, located on left side of   
     humidifier.
 3.  Ionic Bed Inspection
   Remove and inspect one of the ionic beds and inspect the drain screen at the bottom of the  
   tank. If the bed does not appear to be saturated with mineral deposit (a full bed will 
   weigh 1.1 kg (2.42 lbs) dry and if the drain screen is clear, you can reset the Ionic Bed life 
   timer and either change that timer or leave it as it was. Continue on to Step 4.
 If the beds are saturated, remove all of them. Remove any large pieces of scale from the   
   tank. See Page 19 (Replacing the Ionic Beds) for complete instructions.   
  4. Cleaning the Unit
    a. Chemically clean the unit with Rite-Qwik. (If desired.)
      i. Pour 3.75L (1 gallon) of Rite-Qwik into tank followed by 3.8 L (1 gallon) of   
       fresh water. The HC-6500/6700 model requires 7.6 L (2 gallons) of Rite-Qwik  
       and 7.6 L (2 gallons) of water.
      ii. Allow the solution to work until the bubbling action ceases, not to exceed 1   
       hour. While waiting you can proceed with Steps b, c and d.
      iii. Fill the tank with water and drain. (Perform this step several times.) 
    b. Clean the water level electrodes, using an emery cloth. See Page 21 for complete   
     instructions.
    c. Ensure drain lines are free of leaks and secure.
    d. Check inlet screen on fill valve and remove any debris.
    e. Install the new Ionic Beds once you flushed the tank out.