Troubleshooting guide

15
Operation Setup - Continued
Drain Frequency 6
Default: 12 hours 12 (Default)
24
48
96
Real Time
Time Settings
24 Hour Clock
Drain Time
1
5 (Default)
10
Load Default
Reset all to Default? Confirm Cancel
Signal Type
0-10 Vdc (Default)
0-5VDC
1.9V - 3.9V
4-20mA
Sensor Select
Humidistat (Default)
RH Sensor
High Limit Sensor
High Limit Set Point
1% - 99% (85% Default)
Outside Temperature
High Limit Set 1°C / Low Limit Set 1°C
Lowest RH Set Point 15% (Default)
PID Settings PB Proportion Brand 0-500
PID PB 15; PID IRV 125 IRV Integral Reset Value 0-500
PIDF DG 0; PID SI 10 DG Derivative Gain 0-500
SI Interval 0-500
Failure Record
Failure List 01 05-04-01 16:00 (example)
See Page 25 for list of all possible errors. Fill time out to low level
Display the RH graph RH graph of the last 30 days
This menu can be shown when RH sensor is selected.
Set Date and Time
YYY_MM-DD; Time (24 Hr. Format) Date and Time from realtime IC
Save Settings Save User’s Settings
Confirm Cancel
Must be done after any ‘Operation Setup’ menu changes.
2000
2250
2500
2750
3000
No Beds