Troubleshooting guide
15
Operation Setup - Continued
Drain Frequency  6
Default: 12 hours      12 (Default)
 24
 48
 96
 Real Time
 Time Settings
 24 Hour Clock
Drain Time   
 1
 5 (Default)
 10
Load Default
Reset all to Default?      Confirm  Cancel
Signal Type
 0-10 Vdc (Default)
 0-5VDC
 1.9V - 3.9V
 4-20mA
Sensor Select
  Humidistat (Default)  
 RH Sensor
 High Limit Sensor
 High Limit Set Point
 1% - 99% (85% Default)
 Outside Temperature
            High Limit Set 1°C / Low Limit Set 1°C
 Lowest RH Set Point 15% (Default)
PID Settings      PB Proportion Brand 0-500
PID PB 15; PID IRV 125    IRV Integral Reset Value 0-500
PIDF DG 0; PID SI 10    DG Derivative Gain 0-500
 SI Interval 0-500
Failure Record     
Failure List     01 05-04-01 16:00 (example)
See Page 25 for list of all possible errors.    Fill time out to low level
Display the RH graph    RH graph of the last 30 days
 This menu can be shown when RH sensor is selected.
Set Date and Time
YYY_MM-DD; Time (24 Hr. Format)  Date and Time from realtime IC
Save Settings      Save User’s Settings
 Confirm Cancel
 Must be done after any ‘Operation Setup’ menu changes.