Troubleshooting guide

14
Operation Setup
Enter Password 0000 (Default)
Desired RH
(This menu is displayed when RH sensor is selected.)
Desired RH: XX% Default: 50%
Current RH: XX%
LT RT move the cursor UP DN to increase/decrease value
Steam Generation Steam Gen (Default)
Manual Drain (Status 2 will include Drain Drain.)
Manual Fill (Status 2 will include Fill Fill.)
Unit Stop
Modulating Fill Cycle Enabled (Default)
Disabled
If modulating fill cycle is enabled:
Fill Valve Off Time
30 seconds (Default)
Fill Valve On Time
10 seconds (Default)
Failure Reset Failure Reset
Failure Reset? Confirm Cancel
Aquastat
Temperature of water 80°C /176°F
The maximum is 82°C/180°F, the minimum is 4°C/40°F. If
the set point is lower than 40°F, then function is disabled. When
disabled the unit will go into a 3 minute warm-up when turned on.
Network Setup
Disabled Disabled (Default)
Enabled
Secondary ID
Secondary ID 1 (Default) Value: 1 to 127
Communication Type
MODBUS MODBUS (Default)
Baudrate
9600 (Default)
19200
38400
Parity
Even Parity (Default)
Odd Parity
No Parity
Stop Bit
1 Bit(s) (Default)
2 Bit(s)
3 Bit(s)
PSP (includes LonWorks/BACnet)
Password
New Password 0-9 (Default 0000)
A-Z
a-z
End of Life 500
(Run Time Accumulation Hours) 750
1000 (Default)
1250
1500
1750