Troubleshooting guide
14
Operation Setup
Enter Password 0000 (Default)
Desired RH     
(This menu is displayed when RH sensor is selected.)
Desired RH: XX%      Default: 50%
Current RH: XX%
  LT RT move the cursor UP DN to increase/decrease value 
Steam Generation      Steam Gen (Default)
        Manual Drain (Status 2 will include Drain Drain.)
        Manual Fill (Status 2 will include Fill Fill.)
 Unit Stop
Modulating Fill Cycle    Enabled (Default)
 Disabled
        If modulating fill cycle is enabled:  
 Fill Valve Off Time   
 30 seconds (Default)
 Fill Valve On Time
 10 seconds (Default)
Failure Reset      Failure Reset
Failure Reset?  Confirm Cancel
Aquastat
Temperature of water 80°C /176°F
        The maximum is 82°C/180°F, the minimum is 4°C/40°F. If
        the set point is lower than 40°F, then function is disabled. When
        disabled the unit will go into a 3 minute warm-up when turned on.
Network Setup
Disabled  Disabled (Default)
 Enabled
Secondary ID   
Secondary ID 1 (Default)    Value: 1 to 127
Communication Type
MODBUS  MODBUS (Default)
 Baudrate
 9600 (Default)
 19200
 38400
 Parity
 Even Parity (Default)
 Odd Parity
 No Parity
 Stop Bit
 1 Bit(s) (Default)
 2 Bit(s)
 3 Bit(s)
 PSP (includes LonWorks/BACnet)
Password  
New Password      0-9 (Default 0000)
 A-Z
 a-z
End of Life  500
(Run Time Accumulation Hours)  750
 1000 (Default)
 1250
 1500
 1750










