Specifications

Armstrong International
IOM-706
Flo-Direct Water Heater
Page 27 of 45
Pre-Start-Up Checklist
Note: This section to be performed by installer. Consult other information, such as schematics, as necessary.
Heater in permanent location on level surface sufficient for load and anchored
Heater assembled
Transfer pump (if used) in place with flexible water pipe connected
Wiring reconnected
Water pressure switch
Blower motor
UV scanner
Spark rod
Burner modulation, if used
Lower canister float switches
High temperature switch
Transfer pump
Remote storage tank switches or field-supplied relay coil in control panel
Fuel line connected
Adequately sized
Adequately supported
Pressure checked if required
Purged
Water piping connected
Sufficient inlet flow and pressure
Adequately supported
PRV if large pressure swings
Exhaust piping connected
CPVC or stainless steel
No unsealed joints
No bends sharper than 45°
Properly sized (no back pressure)
Adequately supported
Properly terminated
Intake air piping connected or filters installed if necessary
CPVC, stainless steel, or galvanized
Adequately sized
Adequately supported
Proper termination
Storage tank
Properly piped
Float switches installed correctly
Float switches correctly wired to heater
Main power supply properly connected
Three phase
Voltage as specified on nameplate and connections