Installation Guide
A
RMOR DOO
R
TM
INSTALLATION OF WELDED FRAMES
The installation contractor shall have a carpenter 
level and builder’s square.
 Level the head by posi-
tioning the level to the head door rabbet, Figure 4. If 
necessary, adjust for high spots in floor by shim-
ming  under  the  jamb  floor  anchor,  Figure  7. 
Equalize them through an adjustable floor anchor, if 
specified, Figure 13b.  Note, for labeled openings 
the maximum floor clearance is 3/4 in. (19mm).
FIGURE 
4 
LEVELING THE HEAD
With carpenter level check the frame for plumbness
and alignment:  For plumbness, position level 
against both hinge and strike jambs in the rabbet. 
For alignment; Position level against both hinge and 
strike jambs on the stop, adjust as required, Figure 5.
FIGURE 
5
PLUMBING AND ALIGNMENT
SCETION A-A
ALIGNMENT
LEVEL
PLUMB
A
LEVEL
A
LEVE
L
LEVE
L
Once the installer has ensured that the frame is in
the correct position, anchor the jamb to the floor.
Floor Anchors: The fixed floor anchor is welded to 
the base of the jamb, typically secured to the floor
by mechanical fasteners, providing solid anchorage 
for  the  base  of  each  jamb,  Figure  7.  Shimming 
must be used if the floor is not level. This type of 
anchor is not used in existing masonry, preframed 
stud walls or slip-on dry-wall frames, but may be 
provided.
At prepared openings (existing masonry or con-
crete) an additional expansion anchor reinforce-
ment is provided. With pre-framed stud walls or
completed drywall openings an additional base
anchor is included. In both instances these anchors
are located as close to the bottom of the jamb as is
practical.
FIGURE 
7
FIXED FLOOR ANCHOR
With builder’s square, check frame for squareness.
Position square against jamb and head at door rab-
bet, adjust as required, Figure 6.
FIGURE 
6 
SQUARENESS





