6.0 TROUBLESHOOTING
ERROR DESCRIPTION WHAT TO DO
1. No Output and all lights off
Check the power to the unit. The
voltage should be 24VAC/DC at the
power connector with the positive
and negative connected as shown on
the connector label.
Make sure JP1 is in place for DC
voltage
If the Power checks out, call Arjay
Service.
2. 4-20mA output does not track the gas
concentration.
Make sure that the EC-Gold Dual
output mode is set to Analog mode
and not to Discrete Voltage Output
mode. See Controller Settings Sheet
section for details.
Make sure the maximum range of the
remote XMTR is the same as the 2
nd
calibration point. Ex. 20mA=200ppm
CO
Calibration may be required. See the
calibration section for details.
Call Arjay/Enmet Service for Help if
none of the above fixes the problem.