User manual

Model: EC-GOLD
ECGOLDUM17.DOC Rev: 1.7
- 3 -
1.0 INSTRUMENT OVERVIEW
1.1 FEATURES
Single gas transmitter for a large variety of gas types.
Carbon Monoxide sensor has expected life of 5 years min. (3 year guarantee)
Other sensors have expected life of 2 years (1 year guarantee)
Carbon Monoxide sensor has self test feature: periodic & on demand.
Output may be user selectable for analog (4-20mA / 2-10V) or Arjay’s Discrete Voltage Output
(DVO).
Convenient pushbutton calibration.
User selectable for Single or Dual Point calibration
High, Low, and System Fault indication
User selectable High and Low Alarm levels
Modbus protocol via RS-485 for access by Arjay/Enmet Central Access Panel or compatible
system
User specified custom features may be added by contacting Arjay Engineering Ltd.
1.2 DESCRIPTION
The EC-Gold transmitter may be used to sense a large variety of gases including CO, NO
2
, Ammonia,
Chlorine, and Hydrogen Sulfide (H
2
S).
The Carbon Monoxide sensor offers a unique self-test feature, which may be activated either via the
onboard Push To Test pushbutton, or remotely via the Arjay/Enmet Central Access Panel.
The analog output may be field configured either as a 4-20mA / 2-10V output or as an Arjay/Enmet
Discrete Voltage Output (DVO). The DVO is a 4 level output: 0V = ok, Low Alarm = 1.8V, High Alarm =
2.8V, Sensor Fault = 10V. The DVO is a common signaling method: any sensor in a zone triggers the
corresponding Low, High or Sensor Fault alarm at the Arjay/Enmet ISA-66RLU alarm panel.
In Discrete Voltage Output mode, the transmitter may be connected as part of a zone connected to an
Arjay/Enmet ISA-66RLU zone system. In Analog mode, the transmitter puts out a 4-20mA output
proportional to the adjustable Span value.
Independent of the output type selected, the transmitter may also be accessed by an Arjay/Enmet Central
Access Panel (modbus protocol) to form part of a networked gas monitoring system where up to 128
transmitters may be linked on a 2-wire RS485 connection. The networked approach allows more
complex control strategies based on the gas concentrations of a number of transmitters.
Figure 1.0
BLOCK.DSF
UP TO 128 TRANSMITTERS ON THE NETWORK
4-20mA
or
Enmet RLU output
2 Wire RS-485 Network
Alarm LED's
Vents
Sensor access for calibration
Depending on sensor, access is
either from bottom or front.
Push to test
pushbutton (from bottom)
Calibration / Config
pushbutton (from bottom)
2 Wire
24VDC
ENMET EC-GOLD
CENTRAL ACCESS PANEL
(CAP)
EC-GOLD NETWORK APPLICATION