User manual

Model: EC-GOLD
ECGOLDUM17.DOC Rev: 1.7
- 12 -
3.3.6 SETTING THE NETWORK ADDRESS
This value is only used in network applications. Each EC-Gold transmitter connected on a
network must have a unique address. Network problems will result if 2 or more
transmitters have identical addresses.
1. While the Status LED is blinking green, set the DIP switch as follows:
2. Switches 2-6 should be set as per the desired number between 1 and 31. For example
to set the address to 5, set switches 2, 3, and 5, On (Up) and switches 4 and 6 Off
(down). Note: the maximum address that can be entered via the DIP switches is 31.
To set values up to 128, use the Arjay/Enmet EC-Gold hand held calibrator.
3. Press the Cal pushbutton to lock in the value.
3.3.7 EXITING SETUP MODE
After all configuration is done, the setup mode must be exited for normal operation. Also,
calibration cannot be done via the Calibration pushbutton while in setup mode.
To exit setup mode (i.e. Status LED is blinking green), set the DIP switches 1-6 (switch 7 is
not important) to the ON position, and press the Calibration pushbutton. The Status LED
should remain steady green.
IMPORTANT: after exiting the setup mode, do not leave the DIP switches (1-6) in the
ON position as shown above. This will cause entry to Setup mode if calibration is
attempted (i.e. if Calibration pushbutton is pressed). Set at least one switch (1-6) in
the off position. Typically, switch 6 may be set to the OFF position.
FOR EXAMPLE, LEAVE THE DIP SWITCH IN THE FOLLOWING
POSITION FOR NORMAL OPERATION:
THIS COMPLETES THE STARTUP AND CONFIGURATION
12 3456
SET RS-485 ADDRESS FUNCTION
SWs 2-6 set 1 of 31 different addresses
ON
456
= 1
23
= 2
= 3
= 4
= 5
= 6
= 7
= 8
456
= 9
23
= 10
= 11
= 12
= 13
= 14
= 15
= 16
456
= 17
23
= 18
= 19
= 20
= 21
= 22
= 23
= 24
456
= 25
23
= 26
= 27
= 28
= 29
= 30
= 31
12 34567
ON
12 34567
TYPICAL SETTING FOR NORMAL OPERATION
ON