3.0 STARTUP AND CALIBRATION
Figure 3.0
3.1 POWERUP
After the unit has been installed as per the installation procedure in section 2, power up the unit. The
Status indicator should be Green. The red Alarm indicator may be on or off and is not valid until a
successful calibration has been done.
If the Status indicator is red refer to the troubleshooting procedure in section 4.0 for details.
3.2 CONTROL AND FUNCTION SWITCHES
Set up the control and function switches as follows:
3.2.1 Failsafe
Put the selector in the "LO FAILSAFE" position. This will keep the relay energized during normal
conditions. On alarm; the relay will de-energize. A power failure will also cause the relay to de-
energize, signalling an alarm condition.
USERINT.DSF
USER INTERFACE
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
ALARM STATUS
CALIBRATE
DIELECTRIC
LOW HIGH
ALARM DELAY
PROBE IN
-
+
RELAY
LOW HIGH
SENSITIVITY
MODEL
9820/30
DIFFERENTIAL
LEVEL SWITCH
Calibrate Pushbutton
Normally set for HIGH
Alarm delay: 0 - 20sec. Each
switch inc. = 2sec except 6=15
and 7=20. 8&9 not used = 0sec.
Sets Failsafe of relay contacts
Normally set for 3