Technical information

18
installation
Warning
The exhaust gas ducts must not be in contact with or close to inammable material and must not pass throu-
gh building structures or walls made of inammable material.
When replacing an old appliance, the ue system must be changed.
Important
Ensure that the ue is not blocked.
Ensure that the ue is supported and assembled in accordance with these instructions.
150 mm
118
* pente 5 mm par mètre
150
mm
* pente
Installation without extension
Installation with extension
slope 5 mm per metre
Level
Level
slope
Fig. 3
Fitting the Coaxial Flue
(Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall, t
the rubber ue seal into the internal ue turret (see
diagram opposite),
insert the elbow into the socket and rotate to the
required position. Note: It is possible to rotate the
elbow 360° on its vertical axis.
Using the ue clamp, seals and screws supplied (Fig
4) secure the elbow to the boiler.
The 1 metre horizontal ue kit (3318073) supplied is
suitable for an exact X dimension of 753mm.
Measure the distance from the face of the external
wall to the face of the ue elbow (X - Fig 2), this
gure must now be subtracted from 753mm, you
now have the total amount to be cut from the plain
end of the ue.
Draw a circle around the outer ue and cut the ue
to the required length taking care not to cut the
inner ue, next cut the inner ue ensuring that the
length between the inner and outer ue is maintai-
ned. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the
plain end of the ue).
Once cut to the required length, ensure that the ue
is free from burrs and reassemble the ue. If tting
the ue from inside of the building attach the grey
outer wall seal to the ue terminal and push the
ue through the hole, once the wall seal has passed
through the hole, pull the ue back until the seal
is ush with the wall. Alternatively, the ue can be
installed from outside of the building, the grey outer
seal being tted last.
Should the ue require extending, the ue connec-
tions are push t, however, one ue bracket should
be used to secure each metre of ue.
Note: See table for maximum and minimum ue
runs.
In the event that extension pieces need to be
shortened, they must only be cut at the male end
and it must be ensured that the inner and outer ue
remain ush.