Operation Manual

16 GB
Ducting or Recirculation fitting
Ducting fitting
The hood can be ducted to the outside using either rigid or flexible
ducting Ø 120 or 150 mm, the choice of which is left to the installer.
When 120 mm ducting is to be used it will be necessary to install
the reduction flange item
A on the air outlet (fig.5).
When ducting the hood through the side air outlet from the lower
chimney element I it is necessary to insert deflector D into spigot
R to close off the opening that is not being used (fig.6).
Cut the additional spigot P in correspondence with outlets 1 and
2 , which must be formed directly on the piece. Connect the
additional spigot P to the round fan outlet, pushing it downwards,
and fit spigot R to additional spigot P in a similar manner (make
sure that the two additional side recirculation spigots P1 are fitted
to spigot R). Make sure that the height of the assembly R + P
corresponds to the height of the chimney outlet (fig. 7).
If the hood is supplied with the activated charcoal filters
fitted, the filters should be removed (see paragraph on
Maintenance ).
Recirculation fitting
The filtered air is returned to the room through the two
plastic side grills G on the lower chimney element I .
Connect the additional spigot
P to the round fan outlet,
pushing it downwards, and fit spigot R to additional spigot
P in a similar manner (make sure that the two additional
side recirculation spigots P1 are fitted to spigot R). Cut
the additional spigot P in correspondence with outlets 1
and 2 , which must be formed directly on the piece. Make
sure that the height of the assembly R + P corresponds to
the height of the chimney outlet.(fig.7).
Fit the activated charcoal filters inside the canopy (see
paragraph on Maintenance ). Do not fit the venting grilles
until after the chimney has been installed.
D
R
P1P1
P
Fig. 6
R
P1P1
P
G
A
1
8
_
7
1
4
_
0
3
A
1
8
_
7
1
4
_
0
3
A
Fig. 5
Fig. 7