Installation Instructions Type C Boilers G.C.
TABLE OF CONTENTS 1. GENERAL INFORMATION 1.1 General Instructions 1.2 Overall View 2. INSTALLATION 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 Reference Standards Siting the Appliance Overall Dimensions Clearances Mounting the Appliance Electrical Connection Gas Connection Water Connections Flue Connection Room Thermostat Connection Electrical/System Diagrams Water Circuit Diagrams 3. COMMISSIONING 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.
1. GENERAL INFORMATION This manual is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel. Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product. For operating instructions please consult the separate User’s Manual. 1.
6 - With reference to point 4, dismantle and clean the injectors if necessary. 7 - Visual check of the primary heat exchanger: - check for overheating of the exchangers fins; - clean the exhaust side of the exchanger and fan if necessary. 8 - Regulate the gas pressure, ignition pressure, partial flame, maximum flame. 9 - Check proper operation of the heating safety system: - maximum safety temperature; - maximum safety pressure.
2. INSTALLATION The technical information and instructions provided herein below are intended for the installer so that the unit may be installed correctly and safely. 2.1 Reference Standards WATER REGULATIONS These regulations ensure a good supply of wholesome water, and that only approved materials, pipes and fittings are used to convey water. BUILDING REGULATIONS These are a statutory document and take priority over all other regulations and recommendations.
Fig. 2.1 2.3 Overall Dimensions Legend: A = Central Heating Return (3/4”) B = Central Heating Flow (3/4”) C = Gas Inlet (3/4”) D = Domestic Hot Water Outlet (1/2”) E = Secondary return (1/2”) F = Domestic Cold Water Inlet (1/2”) 2.4 Clearances In order to allow for access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the clearance requirements indicated in the diagram below. QT003A 2.
unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom. The local gas region contractor connects the gas meter to the service pipe.
Temperature & pressure relief valve Metal discharge pipe (D1) from temperature & pressure relief valve. to tundish. Tundish 500 mm Max. 300 mm Min. Discharge below fixed grating. (see page 6 for alternative points of discharge). Fixed grating SH005A Metal discharge pipe (D2) from tundish with continuous fall. See Table 2 and worked example. Discharge pipework 1) The tundish must be installed directly below the discharge outlet connection of the boiler.
Air Release Points: These must be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated. It can accept up to 7 l (1.5 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
2.9 BC F G F D HI J A E L K G Fig. 2.6 TERMINAL POSITION A - Directly below an open window or other opening B - Below gutters, solid pipes or drain pipes C - Below eaves D - Below balconies or car-port roof E - From vertical drain pipes and soil pipes F - From internal or external corners G - Above ground or below balcony level H - From a surface facing a terminal I - From a terminal facing a terminal J - From an opening in the car port (e.g.
This procedure must be done as follows: 1 - Remove the air vent intake in the area indicated in Fig. 2.9, by breaking the perforated ring. 2 - Use a tool to grasp the lid and remove it completely. 3 - Clean any burrs or sharp edges with a knife or an appropriate tool. FU013A A Fig. 2.9 Fig. 2.10 FU014A In Fig. 2.11 below, several different types of flue systems are shown. For additional information regarding the flue accessories, please consult the Flue Pipe Accessories manual. Fig. 2.
2.10 Room Thermostat Connection In order to perform this procedure, remove the boiler casing as indicated in section 3.2. Then proceed as follows: 1 TA001A 1 Rotate down the control panel. 2 A 2 Open the cover “A” on the left hand side of the compartment. 3 B 3 Insert the wire for the connection of the room thermostat into the cable clamp “B”, as indicated in photo 3. 4 C 4 Remove the grommet “C” shown in the photo 4, make a hole in it and pass the room thermostat wire through.
2.11 Electrical Diagram AT BT D.H.W. Heating + D.H.W. Heating Flue Test operating modes SE003A T Legend: AT = BT = High Voltage P.C.B. Low Voltage P.C.B. A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Remote Connector Kit Flame Failure L.E.D. Insufficient Water Pressure L.E.D. Water Temperature Indicator L.E.D.s Overheat Thermostat Warning L.E.D. System Reset Button Selector Knob for Operating Mode Domestic Hot Water Temp. Adjustment Central Heating Temp.
2.12 Water Circuit Diagram 19 22 21 20 1 18 2 3 4 5 6 7 8 9 SI003A 17 10 11 12 13 14 15 16 Legend: 1. 2. 3. 4. 5. 6. 8. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 14 Air Pressure Switch Fan Main Heat Exchanger Ignition Electrodes and Detection Electrodes Burner Gas Valve Spark Generator Automatic air release valve Circulation Pump Motorised Valve with by-pass Main Circuit Flow Switch Safety Valve (3 bar) Low pressure switch C.H. expansion Vessel D.H.W.
3. COMMISSIONING 3.1 Initial Preparation MTS (GB) Limited support the initiative. Within the information pack you will find a copy of the logbook. It is important that this is completed in the presence of your customer, they are shown how to us it, and it is signed by them. Please instruct your customer that they must have their logbook with them whenever they contact a service engineer or us. Preliminary electrical system checks to ensure electrical safety must be carried out by a competent person i.e.
3.3 Control Panel Legend: FR004A A Ignition Faliure Reset/Safety Thermostat Reset B L.E.D. for Ignition Faliure C Selector Knob for Summer/Winter/ Flue Test Modes D L.E.D. for Insufficient System Pressure E Domestic Hot Water Temperature Control F Central Heating Temperature Indicating Leds G L.E.D. for Safety Thermostat (overheating) H Heating Temperature Adjustment Knob I L.E.D.
ting for which can range from the minimum thermal power to the maximum: G20 G30-31 5 mbar 19 mbar - the potentiometer for the maximum thermal power for the heating system, maximum thermal power setting (factory set at the maximum value, unless indicated otherwise on the adhesive sticker located in proximity to the potentiometer); - The connection to the diagnosis device (TCS). 3.6 Combustion Analysis The boiler is designed to make it easy to analyse the combustion byproducts.
3.9 Draining the System Draining the heating system. The heating system must be emptied as follows: - Turn off the boiler; - Open the drain valve for the system and place a container below to catch the water that comes out; - Empty the system at the lowest points (where present).
5. 400 MAINTENANCE It is recommended that the following checks be made on the boiler at least once a year: 1 - Check the seals for the water connections; replacement of any faulty seals. 2 - Check the gas seals; replacement of any faulty gas seals. 3 - Visual check of the entire unit. 4 - Visual check of the combustion process and cleaning of the burners if needed. 5 - If called for by check no. 3, dismantling and cleaning of the combustion chamber. 6 - If called for by check no.
6. TECHNICAL INFORMATION GENUS 27 BFFI PLUS CE Certification Thermal Capacity Thermal Power Efficiency of Nominal Thermal Capacity Efficiency at 30% of Nominal Thermal Capacity Heat Loss to the Shell (∆=50°C) Flue Heat Loss with Burner Operating Flue Heat Loss with Burner Off Maximum Discharge of Fumes (methane) Residual Discharge Head Consumption at Nominal Catacity (G20-G25) (15°C, 1013 mbar) (G30-G31) Temp. of exhaust fumes at nominal capacity with methane CO2 Content max/min kW max/min kW % 29.8/12.
Servicing Instructions Type C Boilers G.C.
TABLE OF CONTENTS 1. SERVICING INSTRUCTIONS 1.1 Replacement of Parts 1.2 To Gain General Access 1.2.1 Removing the front panel 1.2.2 Removing side panels 1.2.3 Removing the control panel door 1.3 Access to the Combustion Chamber 1.3.1 Removing the sealed chamber front cover 1.3.2 Removing the combustion cover 1.3.3 Removing the burner and injectors 1.3.4 Removing the electrodes 1.3.5 Removing the main heat exchanger 1.3.6 Removing the air pressure switch 1.3.7 Removing the fan 1.
1. SERVICING INSTRUCTIONS 1.2 To Gain General Access To ensure efficient safe operation, it is recommended that the boiler is serviced annually by a competent person. All testing and maintenance operations on the boiler require the control panel to be lowered. This will also require the removal of the casing. Before starting any servicing work, ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
1.2.2 Removing the side panels: 1. Remove the screws “B” lift outward at the base and then lift off the locating lugs(see fig. 1.3); 1.3 Access to the Combustion Chamber 1.3.1 Removing the sealed chamber front cover 1. Remove the screws “D” (see fig. 1.5) B B D D B D D D D Fig. 1.5 B Fig. 1.3 1.2.3 Removing the control panel door : 1. Open the control panel door and remove screws “C” (see fig. 1.4); 1.3.2 Removing the combustion cover 1. Release the two connection nuts “E”; 2.
1.3.3 Removing the burner and the injectors 1.3.4 Removing the electrodes 1. Undo the nut “G” of the gas pipe (see fig. 1.7) ; 2. Lift up the main burner to free the main gas connection and pull forward very carefully (see fig. 1.8); 3. Remove the injectors (see fig. 1.9); 1. Remove the burner (see fig.1.10); 2. Remove the screws “H” and disconnect the electrode cables slide the electrodes gently downwards (see fig. 1.11-1.12); 3.
1.3.5 Removing the main heat exchanger 1.3.6 Removing the air pressure switch 1. Drain the boiler of water; 2. Release the connection nut “I” connecting the exchanger to the flow pipes (see fig. 1.14); 3. Lower the heat exchanger at its front end and lift forward clear of the ledge at the rear (see fig. 1.15) 4. Pull it straight out. 1. Remove screws “L” on the top of the sealed chamber (see fig. 1.17); 2. Pull upwards the plastic support plug (see fig. 1.18) 3.
1.3.7 Removing the fan 1. Remove the screws “M” (see fig. 1.19); 2. Remove the collar for flue discharge (see fig. 1.20); 3. Disconnect electrical connections ”N”, the silicone pipe “O” and remove screw “P” (see fig.1.21); 4. Pull fan and remove (see fig.1.22); M M M M Fig. 1.19 N N O P Fig. 1.21 Fig. 1.20 Fig. 1.
1.4 Servicing and Removal of the Gas Valve 1.4.1 Setting gas pressures 1 VG001Aa B A Fig. a 2 VG001Ac D C Setting the minimum and the maximum power of the boiler 1. Check that the supply pressure to the gas valve is a minimum of 20 mbar for natural gas. 2. To do this, remove the screw “A” (Fig. a). Fit the pipe of the pressure gauge to the pressure connection of the gas valve “B”. When you have completed this operation, replace the screw “A” securely into its housing to seal off the gas. 3.
GAS BURNER PRESSURE Regulating the heating power for natural gas (G20) CG003A GAS BURNER PRESSURE Regulating the heating power for butane gas (G30) CG002A Regulating the heating power for propane gas (G31) GAS BURNER PRESSURE 40 38 36 34 CG003A TABLE “A” GENUS 27 BFFI PLUS TB002A 9
1.4.2 Removing the spark generator 1. Disconnect ignition leads “Q” by pulling upwards (see fig. 1.23); 2. Remove the screw “R” (see fig. 1.24) with a Pozidrive No. 2 star tip screwdriver; 3. Remove the spark generator by pulling forwards (see fig. 1.25); FR010A SM04A Fig. 1.23 Anti-cycling Device Soft-light Adjustment Max Heating Adjustment Q Fig. e 10.Remove the pipe from the pressure gauge and connect screw “C” to the pressure outlet in order to seal off the gas. 11.
1.5 Access to the Water Circuit 1.4.3 Removing the gas valve Important. ensure gas supply to boiler is turned off. Removing the gas valve 1. Disconnect the cables from the solenoid and modureg; 2. Remove the spark generator (see section 1.4.2); 3. Release the nuts “S” using a 30 mm open ended spanner (see fig. 1.26 - 1.27); 4. Remove the gas valve (see fig. 1.28). Important! Before any component is removed, the boiler must be drained of all water. 1.5.1 Removing the “main circuit flow switch” 1.
1.5.3 Removing the safety valve 1.5.5 Removing the pump 1. Remove the pump pressure switch (see section 1.5.2) 2. Loosen nut “Y” disconnect the safety discharge pipework from under the boiler (see fig. 1.32); 3. Remove the valve. 1. Remove electrical connectione “A1” (see fig. 1.34). 2. Disconnected the two nuts “A2” (see fig. 1.34); 3. Remove the pump. A1 A2 Y Y Fig. 1.32 A2 1.5.4 Removing the automatic air vent Fig. 1.34 1. Remove the automatic air vent “Z” by unscrewing from the pump (see fig. 1.
1.5.7 Removing the domestic expansion vessel Important. Turn off the domestic cold water and drain the storage cylinder. 1. Remove nut “A4” away from the expansion vessel (see fig. 1.38); 2. Remove screws “A5” (see fig. 1.39); 3. Remove expansion vessel (see fig. 1.40). 1.5.8 Removing the overheat thermostat 1. Remove the electrical connector from the overheat thermostat (see fig. 1.41); 2. Pull off the thermostat connections. Then remove the thermostat from the pipe by releasing it’s securing clip.
1.5.10 Temperature and pressure relief valve 1. Ensure electricity is switched off at main isolator; 2. Drain domestic water from cylinder; 3. Loosen nut “A6” and remove the 1/2” nipple (see fig. 1.44); 4. Remove the valve by unscrewing in an anticlockwise direction (see fig. 1.45); A6 1.5.11 Removing the D.H.W. probe This operation is possible with boiler fully assembled. The D.H.W. probe access, is at the bottom right side of the boiler: 1. Ensure electricity is switched of at main isolator. 2.
1.5.12 Removing the diverter valve 1.6.2 Removing the time clock 1. Remove the circlip and pull the diverter valve to the left. (see fig. 1.48); 2. Remove electrical connection by pulling. 1. Remove electrical connections “A7” of the clock (see fig. 1.51); 2. Unscrew the screws “A8” and remove (see fig. 1.52). A7 A8 A8 A8 A8 Fig. 1.51 Fig. 1.48 1.6 Access to the Control System 1.6.1 Checking fuse 1. Remove the right hand inspection cover (see fig. 1.49); 2. Remove fuse from the P.C.B. (see fig.
1.6.3 Removing the P.C.B.s 1. Isolate electricity; 2. Remove the front cover of the boiler; 3. Remove both left and right inspection panels by remove the screws “A9” (see fig. 1.51); 4. Remove the pressure gauge cover; 5. Remove the five screws retaining the facia panel; 6. Disconnect the connection cable”A10” (see fig. 1.52); 7. To remove the 24V P.C.B.: remove the electrical plug connectors and screws “A11” (see fig. 1.53); 8. To remove the 240V P.C.B.
2. FAULT FINDING 1.7 Fault finding guide (flow-chart) It is possible to detect and correct any defect by using the standard fault finding diagrams described in this chapter PRELIMARY CHECKS MAKE SURE THAT: 1 - There is sufficient water in the system 2 - The gas is turned on 3 - The electrical supply is turned on Press the On / Off Button IS THE POWER L.E.D. ON? NO 1 - Check the fuses 2 - Check the power supply cord, plug and outlet 3 - Check/replace the power supply P.C.B. YES D.H.W.
A DOES THE CIRCULATION PUMP COME ON? NO YES POWER TO THE PUMP? NO YES YES 1 - Check if there is air in the system 2 - Check main circuit flow switch operation 3 - Check pressure on the water gauge and fill system to return to 1 bar DOES THE INSUFFICIENT WATER INDICATOR LIGHT COME ON? (within 40 sec.
B IS THE FAN RUNNING? YES NO BOILER SHUTDOWN? YES 1 - Reset the boiler YES 1 - Check/replace different pressure switch for pump 2 - Check/replace wiring 3 - Check/replace P.C.B. wire 4 - Check/replace power supply PCB 5 - Check/replace control PCB NO C PUMP PROTECTION ACTIVATED? NO INTERNAL P.C.B.
C IS THE AIR PRESSURE SWITCH ACTIVATED? 1 - Check flue discharge 2 - Check venturi & small pipes 3 - Check wire for air press.switch 4 - Check/replace air press.
D IS THERE STILL A PROBLEM? YES NO FUNCTIONS NORMALLY LIST OF PROBLEMS 1 Delivery of hot water for domestic use: when the tap is turned on, the bumer goes out. 2 Delivery of hot water for domestic use: the radiators are heated in summer mode 3 Delivery of hot water for domestic use: water temperature is not satisfactory. 4 Delivery of hot water for domestic use: noisy operation. 5 Drop/increase in pressure in primary circuit.
3. ELECTRIC DIAGRAMS Legend: AT = BT = High Voltage P.C.B. Low Voltage P.C.B. A B C D E F G H I J K L M N O Q R S T U V W X Remote Connector Kit Flame Failure L.E.D. Insufficient Water Pressure L.E.D. Water Temperature Indicator L.E.D.s Overheat Thermostat Warning L.E.D. System Reset Button Selector Knob for Operating Mode Domestic Hot Water Temp. Adjustment Central Heating Temp.
4.
GENUS 27 BFFI PLUS Key no. G.C. part no. 5 6 7 7 11 12 13 16 18 19 20 21 24 30 41 44 45 47 57 62 77 78 79 84 85 85 89 93 97 101 104 105 108 121 127 132 133 313 381 382 379816 ARISTON Part No. Description Main exchanger Gasket 3/4" Main burner (natural gas) Main burner (LPG) Gas valve (SIT 845 SIGMA) Spark generator Gasket Motor 3-way valve Hydraulic group Manual vent cock Diaphragm (main flow switch) Main circuit flow switch Safety valve (3bar) Temperature probe (D.H.W.
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiary: MTS (GB) LIMITED MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 Internet: http://www.mtsgb.ltd.uk E-mail: info@mtsgb.ltd.
Users Manual 403
Dear Customer, Thank you for choosing an ARISTON boiler. We guarantee that your boiler is a reliable and technically sound product. This User’s Manual provides detailed instructions and recommendations for proper installation, use and maintenance. Remember to keep this manual in a safe place for future reference i.e. by the gas meter. Your local MTS Servicing Centre is at your complete disposal for all requirements.
1. GENERAL INFORMATION MTS (GB) Limited support the initiative. Your installer will give you, and show you how to use, a logbook which will give you important information about your boiler, and heating system. Please have this logbook to hand whenever you contact a service engineer or us. All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Logbook.
2. OPERATING INSTRUCTIONS CAUTION Installation, start-up, adjustments and maintenance must be performed by a competent person only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided. Improper installation may cause damage or injury to individuals, animals and personal property, for which the manufacturer will not be held liable. To ensure efficient and safe operation it is recommended that the boiler is serviced annually by a competent person.
does not light within the pre-set safety time limit, the red “B” L.E.D. will light up. To reset the ignition system, the reset button “A” must be pressed. Should the system fail to light a second time, check to make sure that the gas cock is open. If the problem persists, contact one of our Authorised Service Centres for assistance.
Installation with a room thermostat: - Turn the “C” selector knob to < >; - Turn on the power supply to the boiler by pressing the On/Off switch ”L”; the green L.E.D. will then turn on; - Turn the thermostat knob “H” to the highest temperature setting. - With this type of installation, the boiler is controlled by a room thermostat . Therefore, it runs until the ambient temperature has reached the temperature setting on the thermostat.
SHUTDOWN PROCEDURE I I To turn off the main burner, simply press the On/Off switch “L”; the green L.E.D. “I” will also turn off. As a precautionary measure, it is recommended that the gas cock located on the bottom of the boiler be turned off as well. L UT008Aa 3. TIME CLOCK Manual switch Summer and winter time setting Reset Enter the hours h Prog .
Automatic Operation Manual Operation Continuous Operation = ON = ON = Continuously ON = OFF = OFF = Continuously OFF The switching times correspond to the program entered. If the current switching mode is changed manually, the next switching time will be carried out automatically again according to the entered switching program. You can only return to automatic mode from the continuously-ON and continuouslyOFF switching modes by pressing the " " key.
Reading the programmed switching times Pressing the “Prog” key displays the programmed switching times until the first free memory location appears in the display “– – : – –”. If you now press the “Prog” key once again, the number of free memory Iocations will be displayed, e.g. “FR 18 ”. If all memory locations are occupied, the display “FR 00 ” appears. Changing the programmed switching times Press the “Prog” key repeatedly until the switching time you want to change is displayed.
4. USEFUL INFORMATION AND TROUBLESHOOTING BOILER SHUTDOWN The boiler unit is equipped with safety devices which intervene in certain situations to shutdown the boiler. Some of these situations are signalled by the unit and can be corrected by the user. SHUTDOWN DUE TO THE FAILURE OF THE BURNER TO LIGHT AUTOMATICALLY B This anomaly is indicated by the red “B” L.E.D. To reset the unit, press and then release the “A” button.
FLUE TEST FEATURE (only for authorised personnel) The “C” Summer/Winter/Flue Test selector knob can be set to < > to bypass temperature adjustment on the heating circuit for the purpose of analysing the fumes produced by combustion. To access this mode, open a water tap or taps so that the flow rate is no less than 8 litres per minute. Then press the “C” selector knob in and turn it from < > or < > to the < >. C UT008Aq 403 WARNING! The flue test feature eliminates the slow-light feature.
Manufacturer: Merloni TermoSanitari SpA - Italy Telephone: (01494) 755600 Fax: (01494) 459775 Internet: http://www.mtsgb.ltd.uk E-mail: info@mtsgb.ltd.uk Technical Service Hot Line: (01494) 539579 Cod.