Technical information
36
settings - adjustment - problem identication menus
menu
sub-menu
Parameter
Description value
default setting
3 BOILER WITH TANK INTERNAL OR EXTERNAL AND SOLAR APPLIANCE CONNECTION
3 0 GE
NERAL SETTING
3 0 0 NOT ACTIVATED
3 0 1 NOT ACTIVATED
3 0 2 NOT ACTIVATED
3 1 Entering access code 222 T
urn the encoder clockwise to select 234 and
press the m
enu button
3 2 SPECIAL SETTING
3 2 0 Anti-legionella function 0=OFF - 1 = ON
This function avoids the formation of the legionella bacterium wich sometimes develops in pipes and water tanks where the temperature is
included
between 20 and 40°C. If the storage temperature remains more than 100 hours less than 59°C and the function is enable, the boiler
is light aan and the storage water is warmed up to 65°C during 30 minutes.
3 2 1 NOT ACTIVATED
Enable only with Clip-In solar connected
(option)
3 2 2 NOT ACTIVATED
3 2 3 Collector delta temp pump ON from 0 to 30°C 8
3 2 4 Collector delta temp pump OFF from 0 to 30°C 2
3 2 5 Minimum collector temp pump ON from 10 to 90°C 30
2 2 6 Collector kick ON or OFF OFF
3 2 7 Recooling function ON or OFF OFF
3 2 8 NOT ACTIVATED
3 2 9 Collector frost protection temperature fr
om -20 to +5°C -20