Technical information

INDIRECT SYSTEMS
For models up to 300 litres a mains supply of 240V, 3kW (13 amps) will be
required for the direct immersion heater. heat resistant cable, round 3 core
2.5mm
2
(to BS) must be used. For High Capacity 500 litre models consult
the wiring diagram on the reverse of the inspection panel.
For indirect controls a 240V, 3 amp supply is required.
On Contract and High Capacity models it is necessary to fit the thermostat
using P.T.F.E tape (Please consult the label on the face of the unit for the
correct location in both cases).
The cables must be clamped in position (as previously stated) and the
control thermostat should be set at 60°C for the reasons above. In addition
to the thermostat there is a thermal cut-out should the thermostat fail. Refer
to
FIG. 2.14.
15
WIRING SCHEME FOR 2 X 2 PORT MOTORISED VALVES
T6360B
ROOM
THERMOSTAT
14
35
22
OR
CM 41
CM 51
A
B
1
5
V4043H
HEATING VALVE
BROWN
5
BLUE
2
GREY
1
ORANGE
10
GREEN/YELLOW
3
V4043H
HOT WATER VALVE
BROWN
8
BLUE
2
GREY
1
ORANGE
10
GREEN/YELLOW
3
Honeywell ST 699B 1002
6 3 N L
Link L-5-8
ST 6400/ST 6300 ST 6200 3 4 N L
Drayton Tempus 7 3 4 N L
Horstmann 425, 525, 527
1 4 E N L
Link L-2-5
Landis & Gyr RWB2
3 4 N L
Glowworm Mastermind
Landis & Gyr RWB20
3 4 N L
Microgyr
Potterton Miniminder 3 4 N L
Potterton EP2000/3000 - 3 4 N L
Link L-5 EP2001/3001
Randall 102/102 E 1 2 E 5 6
Link 3-6
Randall 4033
4 2 E 7 6
Link 1-6
Randall 701, 702
3 1 E N L
Link L-6-5
Sangamo M5 1 8 E 4 3
Link 1-6
Sangamo 410 Form 1
1 8 E 4 3
Link 3-6
PROGRAMMER
6 4 3 2 1
Pegler Sunvic
2 5 E N L
SP 50/100 (Link L-3)
Switchmaster
1 4 N L
Symphony, Sonata
Switchmaster 400, 600 3 1 N L
SWITCHMASTER 805, 900
3 1 N L
Sunvic ET 1451
7 4 E 1 2
Link 2-3-6
Sunvic DHP 2201 6 3 E 1 2
Towerchron FP
6 10 2 1
Link 1-5/4-7-9
Towerchron MP
6 10 2 1
Link 1-4/6-11
Towerchron 2000 HW HTG
N L
ON ON
ACL LS522, LS722 3 4 N L
Randall 922, 972
3 6 E N L
Link L-2-5
Randall 3020 P
4 2 E N L
and 3060
PROGRAMMER
6 4 3 2 1
1
Cylinder
thermostat
Thermal
cut-out
ELEMENT
3 kW 240V
~
Thermal
cut-out
Thermostat
1
8
6
Not
used
L1
240V~
N
P
2
P
2
240V
MAINS INPUT (3 AMP)
L1
N2
E3
240V
MAINS INPUT (13 AMP)
E
L
N
• 1
• 2
• 3
• 4
• 5
• 6
• 7
• 8
• 9
• 10
TYPICAL
JUNCTION BOX
FIG. 2.14
Basic Boilers (see Page 16) L E N L N E
Baxi Solo 2 30PF To 80PF
PL SL E N L L N E
and 30RS to 60RS
Glowworm Economy Plus
7 SL E N L L N E
(remove link SL-9)
Glowworm Spacesaver KFB50
9 12 E N L L N E
(remove link 12-7)
Glowworm Ultimate SS
P SL E N L L N E
(remove link SL - 4)
Glowworm Fuelsaver 100FF
P SL E N L L N E
(remove link 7 - 12)
Halstead Best range 2 1 E N L L N E
Halstead Balmoral range 9 6 E N 12 L N E
Halstead Blenheim range LP 2 E N L L N E
Ideal Mexico Super 2 PL LB E N L L N E
Myson Apollo
PL ON E N L L N E
(remove all links)
Potterton Profile/Suprima PL SL E N L L N E
For ARISTON, Vaillant, Vokèra,
Burco Maxol and other makes, refer
to manufacturers instructions.
BOILER PUMP
9 10 3 2 1 9 10
2
3
Based on Honeywell Controls