Alteas ONE Net User Manual
/ 11
USER’S MANUAL
USER’S MENU
Press the OK button to access to the User’s Menu.
Press the OK button to access the menu and the sub-menu.
Press the programming key
to navigate into the menu and the sub-
menu.
Press the programming key
to change the setting of the
parameters.
Press the OK button to save the new settings.
Press the ESC
button to exit until the normal display screen is
restored.
The various parameters can be accessed and modied using the Ok
button and the programming key
(see g. below).
DHW Settings
Connectivity Settings
CH Settings
Screen Settings
DHW Settings
Connectivity Settings
CH Settings
Screen Settings
a b b c
Operation shutdown error table
Display Description
1 01
Overheating
5 01
No ame detection
1 03
Flow Check Failed
1 04
1 05
1 06
1 07
1 08
Filling Needed
3 05
PCB Fault
3 06
PCB Fault
3 07
PCB Fault
Anti-frost Device.
The anti-frost function acts on the central heating ow tempe
-
rature probe, independently from other regulations, when the
electrical supply is turned on.
If the primary circuit temperature falls below 8°C the pump
will run for 2 minutes.
After the two minutes of circulation (xed) the boiler will check
the following:
a) if the central heating ow temperature is > 8°C, the pump
stops;
b) if the central heating ow temperature is between 4 and 8°C, the
pump will run for another two minutes;
c) if the central heating ow temperature is < 4°C, the burner will re
(heating position) at minimum power until the temperature reaches
33°C, the burner will go out and the pump will continue to run for
two minutes.
If the ow temperature remains between 4-8°C the pump will continue
to run for two minutes for a maximum of 10 times unless a temperatu
-
re above 8°C is detected in the central heating ow, after this the the
burner will re. If lockout is caused by overheat the burner is kept OFF.
The anti-frost device activates only when (with the boiler operating cor
-
rectly):
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.