Installation and Use

46
GB
MONOSPLIT INSTALLATION MULTISPLIT INSTALLATION
1L
2N
S
W
L
N
L
(A)
N
(A)
S
(A)
L
N
3. Fasten the cables using the cable clamp.
4. Put the cover back in place, ensuring it is positioned correctly.
3.3 Connecting to the mains electricity supply
Appliance connection must adhere to European and national standards, and must be protected by a 30 mA differen-
tial switch. Connection to the mains must be permanent (not using a plug) and equipped with an omnipolar switch
complying with current CEIEN standards (contact air gap of at least 3 mm when open, preferably fi tted with a fuse).
Proper connection to an effi cient earthing system is essential for ensuring safe operation of the device.
1. Remove the cover.
2. Connect the conductors to the screw terminals. Screw the terminal board screws tightly to avoid any loosening.
3. Fasten the cables using the cable clamp.
4. Put the cover back in place, ensuring it is positioned correctly.
MONOSPLIT INSTALLATION MULTISPLIT INSTALLATION
1L
2N
S
W
L
N
L
(A)
N
(A)
S
(A)
L
N
3.4 Connection types
MONOSPLIT INSTALLATION
External unit
model
Power supply Switch type Connection cable
Connection
cable type
Power supply
cable
Power supply
cable type
AERES 30 MD0A-O 220-240 ~ 50 Hz 16A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
AERES 35 MD0A-O 220-240 ~ 50 Hz 16A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
AERES 50 MD0-O 220-240 ~ 50 Hz 16A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
AERES 70 MD0-O 220-240 ~ 50 Hz 16A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
MULTISPLIT INSTALLATION
External unit
model
Power supply Switch type Connection cable
Connection
cable type
Power supply
cable
Power supply
cable type
DUAL 55 XD0-O 220-240 ~ 50 Hz 16A 4G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
TRIAL 80 XD0-O 220-240 ~ 50 Hz 25A 4G 1,5 mm
2
H07RN-F 3G 2,5 mm
2
H07RN-F
QUAD 110 XD0-O 220-240 ~ 50 Hz 25A 4G 1,5 mm
2
H07RN-F 3G 2,5 mm
2
H07RN-F
PENTA 125 XC6-O 220-240 ~ 50 Hz 32A 4G 1,5 mm
2
H07RN-F 3G 4 mm
2
H07RN-F
Power supply
Power
supply