Service manual

3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source..... Voltage Rating 400V - 3N - 50Hz........ 400 V
Control Circuit 230 V 50 Hz
Cooling
Capacity
kW 6.15
BTU/h 21000
Air circulation (High) m
3
/h 830
Moisture removal (High) Liters/h 3.3
Available voltage range V 342 to 418
Running amperes A 4.8
Power input W 2800
Power factor % 84
C.O.P. W/W 2.20
Compressor locked rotor amperes A 28
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407c / 2,450
Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 58 / 55 /52
Outdoor – Hi dB-A 67
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 15.88(5/8)
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 835
Width mm 995 850
Depth mm 206 305
Package dimensions Height mm 276 913
Width mm 1,070 1000
Depth mm 363 400
Weight Net
kg 12.0 67.0
Shipping
kg 15.0 76.0
Shipping volume m
3
0.11 0.37
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit AWR522CL
Outdoor Unit AER522SC3
Refrigerant tube kit/accessories Optional/Hanging wall bracket