Service manual

10. TROUBLESHOOTING
10-1. Check before and after
troubleshooting
10-1-1. Check power supply wiring.
Check that power supply wires are correctly connected
to terminals L and N on the terminal plate in the
outdoor unit.
10-1-2. Check inter-unit wiring.
Check that inter-unit wiring is correctly connected to
the indoor unit from the outdoor unit.
10-1-3. Check power supply.
Check that voltage is in specified range
(±10% of the rating).
Check that power is being supplied.
10-1-4. Check lead wires and connectors in
indoor and outdoor units.
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly
connected.
Check that wiring is correct.
60
WARNING
Hazardous voltage can cause ELECTRIC
SHOCK or DEATH. Disconnect power or turn
off circuit breaker before you start checking
or servicing.
1
Indoor
unit
Outdoor
unit
Inter-unit
wiring
Power supply:
380 V – 400 V
3N ~ 50 Hz
N
2
L1
L2
L3
L1
L2
L3
N
Ground
Ground
1
2
4 4
Check that power supply wires are correctly connected
to terminals L1, L2 , L3 and N on the terminal plate in
the outdoor unit.
THREEPHASE MODELS
380V – (400V)
380V – (400V)
380V – (400V)
L1
L2
L3
N
220V – (230V)
THREEPHASE MODELS