Service manual

51
8-4 LOW AMBIENT FAN SPEED CONTROL < FOR AER518SCL3 >
This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the
compressor when the outdoor temperature is very low.
When the air temp. thermistor (TH4) on the outdoor units detects a change in temperature, the solid state relay
(SSR) inside the electrical component box activates to control the fan speed accordingly.
As the outdoor temperature decreases and drops below 28.0°C, the outdoor fan speed starts to gradually slow
down following an oblique line as in the diagram below.
Outdoor fan speed changes more or less according to the room temperature.
When the outdoor temperature goes above 30.0°C, this fan speed control does not work.
Conditions: Room temperature 19.4°C DB/13.9°C WB
800
1000
600
400
200
0
–10 –5 0 5 10 15 20 25 30 35
28.0
30.0
900 rpm
(HIGH)
Outdoor ambient temperature (°C)
Outdoor fan speed (rpm)
Coil temp.
thermistor
(TH3)
Air temp.
thermistor (TH4)