Service manual

Outdoor Unit AER518SCL3
Solid State Relay (SSR) G3L-205TL-TS1
Input
Rated voltage DC 12V
Control voltage range DC 0V to 6.4V
Load voltage range AC 75V to 264V, 50Hz
Negative Phase Relay (47C) RDR-S400
Rating AC 415V, 3-phase 50Hz
Contact rating AC 400V, 1A
Operation Positive phase: ON
Negative phase: OFF
Electro Magnetic Contactor (MG) HE-10TB TH-5A
Magnetic contactor
Coil rating AC 220–240V, 50Hz / AC 240–260V, 60Hz
Coil resistance (at 25°C) 1,260 ± 10%
Contact rating (Main) AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes 5A
Transformer (TR2) ATR-J105-I
Rating Primary AC 230V, 50Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance (at 22°C) Primary (WHT – WHT):205 ±10%
Secondary (BRN – BRN):2.0 ±10%
Thermal cut-off temp. 150°C
Thermistor (Coil sensor TH3 / Air sensor TH4) PBC-41E-S4 / PBC-41E-S8
Resistance k –20°C 40.1 ± 5% 20°C 6.5 ± 5%
–10°C 24.4 ± 5% 30°C 4.4 ± 5%
0°C 15.3 ± 5% 40°C 3.0 ± 5%
10°C 9.9 ± 5% 50°C 2.1 ± 5%
19
TH-5A
Power Relay HH62S DC24V
Coil rating DC 24V
Coil resistance k(at 23°C) 650 ± 10%
Contact rating AC 250V, 10A