Service manual
23
NOTA
1)ROOM TEMPERATURE CONTROL
Cooling
•Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
F
FUNCTION
•The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at
least 3 minutes.
To protect the compressor from stalling out when trying to start against the high side refrigerant pressure,
the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
•As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of
compressor operation.
•Thermo ON: When the room temperature is above T + 1°C (T°C is set temperature).
Compressor ➔ ON.
•Thermo OFF:When the room temperature in equal to or below set temperature T°C.
Compressor ➔ OFF.
MORE THAN
5 MINUTES
THERMO OFF
MORE THAN
3 MINUTES
THERMO
ON
THERMO
OFF
MORE THAN
5 MINUTES
3 MINUTES 5 MINUTES
THERMO
ON THERMO
OFF
WITHIN
3 MINUTES
WITHIN
5 MINUTES
ONOFFONOFFON
ROOM TEMPERATURE
OFFON ONOFFON
SET SPEED (MANUAL)
SET T + 0,5 ϒC
TEMPERATURE T ϒC
COMPRESSOR
OUTDOOR
FAN
INDOOR
FAN