Technical data
25
Water - level alarm (condensate) is blinking
Malfunctioning of the condensate drainage system to the outdoor unit
NOTE - In case of emergency the air conditioner can work by draining the condensate from the back
little pipe into a rather short container, extract the little pipe and remove the cap.
YES
NO
The condensate drain pipe in the flexible
connection pipe is bended or obstructed
Check electrical components (connec-
tions and continuity of internal wiring)
Remove the obstruction
Replace drain pump
DEFECTIVE
Replace limit float switch (MS)
DEFECTIVE
YES
Check limit float switch
(MS)
YES
Check drain pump motor
(PC)
C
D
Check setting temperature
Outdoor unit does not run when air conditioner is in following conditions.
● 
When the room temperature is below the setting temperature.
● 
During freeze prevention.
Outdoor unit does
not run
NO
Is room temperature too low?
Check room sensor (thermistor TH2).
Try to lower setting temperature by tem-
perature setting button
OK
PCB assy is defective.
Only outdoor unit and compressor do not run