Technical data
9.4 Overheat outdoor exchanger
During cooling operation as soon as the outdoor coil temperature (OCT) increases, compressor speed
is reduced in order to avoid heat exchanger overheating. System stops compressor operation when OCT
reaches 65 °C
9.5 Compressor discharge temperature
During operation, as soon as the discharge temperature increases, (CDT) compressor speed is reduced
in order to avoid overheating of the motor. Compressor is stopped when CDT reaches 111°C
9.6 Compressor power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system an
d
kept operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
9.7 Compressor power-module overcurrent
Operation is automatically stopped in case of current driven to each motor phase greater than 9
A