Technical data

5 Dry Mode Operation
Dry operation remove moisture from indoor air running, in cooling mode, at a low level without reducin
g
the ambient temperature. This is done cycling ON and OFF the unit according to table below.
ROOM DRY LEVEL
TEMP
SPT+2°C LEVEL 0 Operation according to COOLING mode
CM on at constant speed
< SPT+2°C LEVEL 1 FMO on at constant speed
SPT-1°C FMI switches between L and OFF every 30 second
s
RV off
CM switches 9 minutes off and 3 minutes on
< SPT-1°C LEVEL 2 FMO switches 9 minutes off and 3 minutes ON
15°C FMI switches between L and OFF every 30 second
s
RV off
CM off
< 15°C DRY OFF ZONE FMO off
FMI off
RV off
SPT = Set Point Temperature
6 Fan Mode Operation
With this mode, the indoor fan is turned on while CM and FMO stay off all the time. The user can
select between 3 speeds: HIGH, MEDIUM and LOW.
7 Auto Fan speed
With this option selected, the indoor fan speed changes automatically according to the compressor
speed as shown in the following graph
s
In heating, to prevent the supply of cool air, the FMI speed is setted as shown only if the indoor
coil temperature ICT 34°C ( see COLD DRAFT PREVENTION feature for details )
If RAT goes over SET POINT by 1°C or less, for 1 hour, FMI is forced to LOW. If after
1 hour, RAT is still over SPT, FMI and compressor switch off.
Pagina 11