Install Instructions

7
Figure #1
V - DPM-2 CONTROL MOUNTING INSTRUCTIONS
Mount the Argo DPM-2 Control vertically on a solid wall or parti-
tion. For your convenience it is recommended that the control be
mounted as close as possible to the device being controlled, how-
ever it should never be mounted more then 75 feet away. Select a
location that is easily accessible for installation and service.
NOTE: To reduce the possible transformer hum and relay noise
that is sometimes amplied by mounting surfaces such as sheet
metal, plasterboard, and similar materials, place rubber or felt
washers between the case and the mounting surface.
Position the control and mark the mounting holes.1.
Start screw (not provided) in the keyhole type mounting 2.
hole in the upper right hand corner. Tighten the screw down
to about ⅛” (3mm) from the surface.
Hang and level the control on the screw and start the bot-
3.
tom left hand screw.
Tighten all screws.
4.
IMPORTANT: Install out-
door sensor (provided with
DPM-2) on the north side or
a shaded side of the build-
ing. Locate a minimum of
10 feet above grade and not
near any location where in-
ternal heat could affect the
sensor rating, such as win-
dow, doors, exhaust vents
or fans. (Figure #1)
Outdoor Sensor Installation