X - TROUBLESHOOTING
OUTDOOR SENSOR WATER SUPPLY SENSOR
Degrees Ohms Degrees Ohms
5 758 149 1368
14 789 158 1413
23 822 167 1459
32 855 176 1506
41 889 185 1554
50 924 194 1602
59 960 203 1652
68 997 212 1702
77 1035 - -
NOTE: The Outdoor Sensor and Water Supply Sensor
are interchangeable and may be reversed to assist the
troubleshooting process.
EXAMPLE: If the water sensor reads 1500 ohms and you
estimate that the water is about 175°F, the water sensor is okay.
If the meter reads 1400 ohms or 155°F, you might suspect the
thermal connection between sensor and the pipe.