Technical data

2
2 - 11
Design of Mini Multiset
1. Model Selecting and Capacity Calculator
1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
92 90 88 86 84 82 80 78 76
0 10 20 30 40 50 60 70 80 90 100 110
120 130
140 150
<Cooling>
<Heating>
Elevation difference (m)
Equivalent length (m)
50
40
30
20
10
0
10
20
30
40
*1
97 96 95 94 93 92 91
0 10 20 30 40 50 60 70 80 90 100 110
120 130
140 150
50
40
30
20
10
0
10
20
30
40
Elevation difference (m)
*1
98
99
100
%
Equivalent len
g
th (m)
Base capacity
change rate (%)
Base capacity
change rate (%)
94
100
%
98
96
Inverter model rated performance values
Cooling HeatingItem
Model (SPW-)
AES 04 MMIH
AES 05 MMIH
AES 06
MMIH
Cooling
capacity
(kW)
Power
consumption
(kW)
Heating
capacity
(kW)
Power
consumption
(kW)
11.2
14.0
15.5
2.76
3.83
4.57
12.5
16.0
17.6
2.88
3.90
4.58
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 (3))
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
Outdoor intake air
20 15 10 8 6 5 4 2 10123456
temp. (°C WB RH 85%)
Correction
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
coefficient