Install Instructions

15
ARM “TANKLESS COIL” APPLICATION
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
REMOVE factory installed jumper
between ZC and ZR.
A tankless coil requires a boiler aquastat. Each zone thermostat will
signal the ARM to start its zone circulator and send a call for heat to the
boiler aquastat. If boiler temperature drops below the low limit setting,
all circulating will cease until temperature of boiler water is increased.
JUMPER
Remove factory-installed jumper between terminals ZC and ZR.
Connect terminals ZC and ZR to corresponding ZC and ZR termi-
nals on boiler aquastat. Circulators for zones connected to the ARM
relays will not operate if the boiler tankless coil aquastat low limit is
not satised. Terminals ZC-ZR are 120 VAC connections.
PRIORITY
Circulators for additional zones will not operate when zone 1 (pri-
ority) circulator is actuated. (Priority switch is
ON.) When priority
switch is not ON, all zones operate independently of each other.