Specifications

ASS
105
4-Way Air Discharge Semi-Concealed Type
(ASS Type)
Checking the unit position
(1) Check that the ceiling hole is within this range:
860 × 860 to 910 × 910 mm
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to deter-
mine the positioning of the unit on the ceiling sur-
face. If the positions of the ceiling surface and unit
do not match, air leakage, water leakage, flap
operation failure, or other problems may result.
CAUTION
Never place the panel
face-down. Either hang it
vertically or place it on
top of a projecting
object. Placing it face-
down will damage the
surface.
Do not touch the flap or
apply force to it.
(This may cause flap
malfunction.)
must be within the range of 12 17 mm.
If not within this range, malfunction or other trouble may result.
A
Ceiling side
Main unit
Ceiling opening
dimension
A
Fig. 9-11
Wing
Fig. 9-12a
Fig. 9-12b
2
Fig. 9-14
9-7. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 9-12b, 9-13 and 9-14)
a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 9-12b)
b) Slide the air-intake grille catches in the direc-
tion shown by the arrows to open the grille.
(Fig. 9-13)
c) With the air-intake grille opened, remove the
grille hinge from the ceiling panel by sliding it in
the direction shown by the arrow .
(Fig. 9-14)
(2) Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow to remove the corner cover.
(Fig. 9-15).
1
2
1
Corner cover
Ceiling panel
Strap
Push
1
Corner cover
Fig. 9-15
Air-intake grille
Ceiling panel
Air-intake grille hinge
1
1
Fig. 9-13
Latch
Screw